Chapter 4: Smoke control acceptance and testing 
VM-1 Smoke Management Application Guide  53 
The operational testing of each individual building 
system component is performed to determine if smoke 
zones or areas are complete exclusive of VM-1 SCS 
programmed commands. These operational tests 
normally will be performed by various trades before 
interconnection to the VM-1 SCS is made. 
It should be certified in writing by the responsible trades 
that each system component’s installation is complete 
and the component is functional including relays 
installed by others for interconnection to the VM-1 SCS. 
Each component test should be individually 
documented, including such items as speed, voltage, 
and amperage. 
Because smoke control systems are usually an integral 
part of building operating systems, testing of the building 
system should include the following subsystems to the 
extent that they affect the operation of the smoke control 
system: 
•  Energy management system 
•  Building management and security system 
•  HVAC equipment 
•  Electrical equipment 
•  Temperature control system 
•  Power sources and standby power for fans and 
damper 
•  Automatic suppression systems 
•  Automatic operating doors and closures 
•  Emergency elevator operation 
In most applications building control components to the 
smoke control system are required to operate from the 
building’s emergency power system as a backup to 
primary power. The electrical load required for motors in 
fan control circuits and status indicators from the 
emergency power must be provided for in emergency 
power design. 
VM-1 SCS/FSCS component testing: Components 
activated by the smoke control system to be tested 
include: 
•  Dedicated smoke control systems 
•  Nondedicated smoke control systems  
•  Fire alarm systems installed under NFPA 72 
The FSCS series graphic annunciator must receive 
power from other sources. The cabinet does not contain 
batteries for emergency power. 
Acceptance testing 
The intent of acceptance testing is to demonstrate that 
the final integrated system installation complies with the 
specified design and is functioning properly. One or 
more of the following should be present to grant 
acceptance: 
•  Building system designer 
•  VM-1 SCS designer/installer 
•  AHJ 
All documentation from component testing should be 
available for inspection. 
Building test equipment 
The following equipment may be needed to determine 
air flows and compartmentation as a part of smoke 
control acceptance testing: 
•  Differential pressure gauges, inclined water or 
electronic manometer 
•  Scale suitable for measuring door-opening force 
•  Anemometer, including traversing equipment 
•  Ammeter 
•  Flow-measuring hood (optional) 
•  Door wedges 
•  Tissue paper roll (for indicating direction of airflow) 
•  Signs indicating a test of the smoke control system 
is in progress 
•  Walkie-talkie radios for coordinating equipment  
VM-1 SCS test equipment 
Required Tools: 
•  Slotted screwdriver, insulated 
•  Digital multimeter 
•  12 in. (30.5 cm) jumper lead with alligator clips 
•  Panel door key