Glossary 
64  VM-1 Smoke Management Application Guide 
nondedicated system: A smoke control system that 
shares components with other air moving 
equipment. When the smoke control mode is 
activated, the operating of the building's air moving 
equipment changes in order to accomplish the 
objectives of the smoke control design. 
pressurized stairwell: A type of smoke control system in 
which stair shafts are mechanically pressurized with 
outdoor air to keep smoke from contaminating them 
during a fire event. 
SCS: Acronym for smoke control system. See also 
smoke control system. 
separated spaces: Spaces within a building that are 
isolated from large-volume spaces by smoke 
barriers that do not rely on airflow to restrict the 
movement of smoke. 
smoke: The airborne solid and liquid particulates and 
gases evolved when a material undergoes pyrolysis 
or combustion, together with the quantity of air that 
is entrained or otherwise mixed into the mass. 
smoke barrier: A membrane, either vertical or horizontal, 
such as a wall, floor, or ceiling assembly, that is 
designed and constructed to restrict the movement 
of smoke. A smoke barrier might or might not have a 
fire resistance rating. 
smoke control mode: A predefined operational 
configuration of a system, zone, or device for the 
purpose of smoke control. 
smoke control system: An engineered system that uses 
mechanical fans to produce airflow and pressure 
differences across smoke barriers to limit and direct 
smoke movement. 
smoke damper: A UL Listed device designed to resist 
the passage of air or smoke. Smoke dampers are 
installed in ducts or smoke barriers separating floor 
or smoke zones. A fire barrier constructed to limit 
smoke may also serve as a smoke barrier and may 
use a combination fire and smoke damper that is 
also UL Listed. Systems serving more than one floor 
with a capacity greater than 15,000 cfm are required 
by NFPA 90A to have smoke dampers installed to 
isolate the air handling equipment, including filters, 
to restrict the circulation of smoke. 
smoke exhaust system: A mechanical or gravity system 
intended to move smoke from a smoke zone to the 
exterior of a building, including smoke removal, 
purging, and venting systems, as well as the 
function of exhaust fans utilized to reduce the 
pressure in a smoke zone. 
smoke proof enclosure: A continuous stairway which is 
enclosed from top to bottom by a 2-hour firewall and 
exits to the exterior of a building. Entry into the 
stairway must be through vestibules or outside 
balconies on each floor. The design must limit 
smoke entry and include ventilation which is natural 
or mechanical. 
smoke zone: The smoke control zone in which the fire is 
located. 
stack effect: The vertical airflow within buildings caused 
by the temperature-created density differences 
between the building interior and exterior or between 
two interior spaces. 
tenable environment: An environment in which smoke 
and heat is limited or otherwise restricted in order to 
maintain the impact on occupants to a level that is 
not life threatening. In a zoned smoke control 
system, pressure differences are used to maintain a 
tenable environment in an area intended to protect 
building occupants while evacuation is taking place. 
UBC: Acronym for uniform building code. 
UUKL: The Underwriters Laboratories (UL) 
complementary product category designation for 
smoke control system equipment. 
VAV: Acronym for variable air volume. 
zoned smoke control: A smoke control system that 
includes smoke exhaust for the smoke zone and 
pressurization for all contiguous smoke control 
zones. The remaining smoke control zones in the 
building also may be pressurized.