Why is my KiloVault HLX battery bank suddenly shutting off?
- RRoy HooverAug 3, 2025
The battery bank might be shutting off because one or more of your batteries are not at the same state of charge as the others. To resolve this, individually charge the batteries to the same voltage, ideally between 13.8V-14.4V on the LiFePO4 charging curve. Alternatively, discharge them to between 11.5-12.5V. A simple 12V AC charger capable of achieving 14.0-14.4V may be useful. Another possible reason is that the load is exceeding the current capabilities of the batteries. To fix this, add an additional parallel row of KiloVault® batteries to increase the current capacity.