Mounting Set
Statutory provisions
TheDevicemustbeinstalledandoperatedaccordingtothefollowingnormsandcountryspecicdirectivesandprovisions:
DIN EN 12828
DIN 1988
DIN 4708
DIN 4753
DIN 4757
DIN 18380
DIN 18381
DIN 18382
DIN EN 12975
VDE 0100
VDE 0185
VDE 0190
ÖNORM H5195
Material damage
Deviations from the values stated in table 1 may lead to damages and functional limitations of the device.
Noncompliance with these values leads inevitably to a loss of guarantee.
ForoperatingtheFreshWaterStation,thefollowingspecicvalueshavetobeadhered:
Dissolved matter Unit Speci c values (copper brazed)
pH-value 7-9 (considering Saturation index)
Saturation index (delta pH-value) -0,2 < 0 < +0,2
Degree of hardness °dH 6-15
Conductivity μS/cm 10...500
Filterable matter mg/l <30
Free chlorine mg/l <0,5
Hydrosulde(H2S) mg/l <0,05
Ammoniac (NH3/NH4+) mg/l <2
Sulfate mg/l <100
Hydrocarbonate mg/l <300
Hydrocarbonate/Sulfate mg/l >1,0
Sulde mg/l <1
Nitrate mg/l <100
Nitrite mg/l <0,1
Iron, solute mg/l <0,2
Manganese mg/l <0,1
Free aggressive carbonic acid mg/l <20