Document No.:KE-4010-11 Page: 53/58
8.2FSWmanualoperatorunitscanbemountedonTypeFASspringreturnactuatorsforAIR-FAIL-CLOSE
modeasfollows.
(1)RotatethehandwheelofaFSWmanualoperatorunitclockwisetillitcompletelystops(Fig.13).
Fig.13
Fig.14
(2)MountanO-ringonthebottomoftheFSWunit(Fig.14).
(3)Equalizethehousingpressurewiththeatmosphericlevel,andremoveanendcoverfromTypeFASspring
returnactuator(Fig.15).
Fig.15
(4)MounttheFSWunitontheendcoveropeningofthehousing,ensuringthattheO-ringdoesnotswellout
throughthecontactoftheunitwiththehousing(Fig.16).
Fig.16
(5)PressurizetheactuatorwiththeactualoperationpressurethroughPort[O]and[S]andcheckexternalair
leakagewithsoapsolution. Wipeoffthesoapsolutionafterwards.
(6)Energizetheactuatorfortrialoperationtoensuretrouble-freefunction. Werecommendtocarefullyread
Section8.4oftheoperationmanualbeforemanuallyoperatingspringreturnactuators.
O-ring<45F>
FSWmanualoperatorunit