EasyManuals Logo

Klein Tools MM6000 User Manual

Klein Tools MM6000
2 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
GRAPHICS DRAWING NAME: MM6000 Manual ENG.indd
GRAPHICS PART NUMBER: XXXXXX ECN NUMBER.: 00000
PACKAGING DWG. REF.: VENDOR SUPPLIED Revision: A 10.11.12
ENGLISH
www.kleintools.com
Instruction
Manual
For Professionals...Since 1857
®
ENGLISH
MM6000
• TRUERMS
• BACKLITDISPLAY
• BARGRAPH
• LEADSTORAGE
• MAX/MIN
• 3-5/6DIGIT
6000COUNTLCD
• AUTO/MANUAL
RANGE
• AUTOHOLD
HOLD
Apo
AUTO
RANGE
TRMS
A-HOLD
SYMBOLSUSEDONLCD
~
ACMeasurement
DCMeasurement
-
NegativeDCValue
AT
AutoRangeActive
O
.L.
Overload:RangeExceeded
Apo
AutoPower-OffActive
LowBattery
HOLD
HoldActive
MIN
MinimumReading
M
AX
MaximumReading
%
DutyCycleMode FrequencyMode
V
VoltageMeasurement
A
CurrentinAmps
Ω
ResistanceinOhms DiodeTest
F
CapacitanceinFarads ContinuityTest
Relative/ZeroMode
n
Nano10
-9
µ
Micro10
-6
m
Milli10
-3
k
Kilo10
3
M
Mega10
6
°F
DegreesFahrenheit
°C
DegreesCelsius
A- HOLD
Auto-HoldActive
LOW
Z
LowImpedance
ELECTRICALSPECIFICATIONS
DCVoltageMeasurement
Range Resolution Accuracy
600mV
˜
600V 0.1mV
˜
0.1V ± (0.2% + 5 digits)
1000V 1V ± (0.5% + 10 digits)
OverloadProtection: 1000V InputImpedance(Nominal): >10MΩ, <100pF
InputImpedance(LOWZ): >3kΩ, <200pF, up to 600V RMS
ACVoltageMeasurement
Range Resolution
Accuracy
40Hz ~ 400Hz
Accuracy
400Hz ~ 2kHz
600mV 0.1mV
± (0.75% + 5 digits)
± (2.5% +10 digits)
6V ~ 600V 1mV ~ 0.1V ± (2.0% + 8 digits)
1000V 1V ± (0.75% + 8 digits) ± (2.0% +8 digits)*
Continued on next page.
OverloadProtection: 1000V RMS InputImpedance(Nominal): >10MΩ, <100pF
InputImpedance(LOWZ): >3kΩ, <200pF, up to 600V RMS
FrequencyResponse: 40 to 2kHz Response: True RMS
*Accuracy for 400Hz ~ 1kHz range only.
DCCurrentMeasurement
Range Resolution Accuracy
600µA ~ 400mA 0.1µA ~ 0.1mA ± (1.0% + 5 digits)
6A ~ 10A 1mA ~ 10mA ± (1.5% + 5 digits)
OverloadProtection:µAmA:400mA (F440mA/1000V fuse) /AInput:10A(F11A/1000V fuse)
ACCurrentMeasurement
Range Resolution
Accuracy
40Hz ~ 2kHz
600µA ~ 400mA 0.1µA ~ 0.1mA ± (1.2% + 5 digits)
6A ~ 10A 1mA ~ 10mA
± (1.8% + 5 digits)
OverloadProtection:µAmA:400mA (F440mA/1000V fuse) /AInput:10A(F11A/1000V fuse)
Frequency: 40 to 2kHz Response: True RMS
ResistanceMeasurement
Range Resolution Accuracy
600Ω
˜
6MΩ 0.1Ω
˜
0.001MΩ ± (1.0% + 5 digits)
50MΩ 0.01MΩ ± (1.5% + 10 digits)
OverloadProtection: 600V RMS
CapacitanceMeasurement
Range Resolution Accuracy
60nF 0.01nF
± (3.5% + 6 digits)
600nF ~ 6000µF 0.1nF ~ 1µF
OverloadProtection:600V RMS
FrequencyMeasurement
Range Resolution Accuracy
99.99Hz
˜
399.9kHz 0.01Hz
˜
0.1kHz ± (0.1% + 3 digits)
OverloadProtection: 600V RMS Sensitivity: 2.5V RMS
DutyCycleMeasurement
Range Resolution Accuracy
1.0
˜
99.0% 0.1% ± (0.2% per kHz + 0.1% + 8 digits)
OverloadProtection: 600V RMS Sensitivity: < 50V RMS
FrequencyRange: 0.5Hz to 10kHz
DiodeTest
OverloadProtection Range TestCurrent OpenCircuitVoltage
600V RMS 6.0V DC 0.25mA
<
1.8V DC
ContinuityTest
OverloadProtection OpenCircuitVoltage Threshold(Appx.)
600V RMS
<
0.44V <40Ω
TemperatureMeasurement
Range Resolution Accuracy
-58 ~ 600°F 0.1°F ± (1.0% + 5.4°F)
-50 ~ 600°C 0.1°C ± (1.0% + 3.0°C)
600 ~ 1832°F 1°F ± (1.0% + 5.4°F)
600 ~ 1000°C 1°C ± (1.0% + 3.0°C)
OverloadProtection: 600V RMS K-typeThermocoupleAccuracy: Not specified
Specifications subject to change.
WARRANTY
See www.kleintools.com, contact Klein Tools at 1-877-775-5346, or visit a
distributor for warranty information.
CLEANING
Turn instrument off and disconnect test leads. Clean the instrument by using
a damp cloth. Do not use abrasive cleaners or solvents.
STORAGE
Remove the batteries when instrument is not in use for a prolonged period
of time. Do not expose to high temperatures or humidity. After a period of
storage in extreme conditions exceeding the limits mentioned in the General
Specifications section, allow the instrument to return to normal operating
conditions before using it.
DISPOSAL/RECYCLE
Caution:This symbol indicates that equipment and its accessories
shall be subject to a separate collection and correct disposal.
CUSTOMERSERVICE
DONOTapplyvoltagetothermocouple.
• Fahrenheit range: -58° to 1832°F (Celsius range: -50° to 1000° C).
8. Temperature:
Features:
MAX/MIN RELHOLD
TestingFuse:
• When selecting uA or mA/A functions the meter will indicate
LEAd” if the test leads are not properly connected to the meter.
• Note: This message remaining on the screen after properly
connecting the test leads is an indication that the fuse is open.
KLEINTOOLS,INC.
450 Bond Street
Lincolnshire, IL 60069
1-877-775-5346
www.kleintools.com
Rev A 1/13 139750
7. Frequency(Hz)/DutyCycle:<400kHz
Features:
HOLD
6. LowImpedance(LOWZ):<600V
DONOTuse(LOWZ)modeatvoltagesgreaterthan600V.
• Press SELECT to choose AC or DC Voltage.
• Use Low Impedance (LOW Z) mode to reduce ghost voltages.
• See AC/DC Voltage instruction.
Capacitance Features:
HOLD
Safelydischargecapacitorbefore
measurement.
• Reading may take up to 60 seconds
for large capacitors.
AUTOHOLD
4007036

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Klein Tools MM6000 and is the answer not in the manual?

Klein Tools MM6000 Specifications

General IconGeneral
BrandKlein Tools
ModelMM6000
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals