EasyManuals Logo

Kohler 12EFKOZD User Manual

Kohler 12EFKOZD
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #95 background imageLoading...
Page #95 background image
TP-7044 6/23 95
Section or
Publication
Reference*
Alternator
Gen. S/M or
W/D
Gen. S/M
Gen. S/M
Electrical System (DC Circuits)
Eng. O/M, S/S
Eng. S/M
W/D
Operation
Section
ATS - Automatic Transfer Switch; Eng.
- Engine; Gen.
- Generator Set; I/M
- Installation M
anual; O/M
- Operation Manual;
M/M Maintenance Manual; S/M
- Service Manual;
S/S - Spec Sheet; W/D
- Wiring Diagram Manual
Have an authorized service distributor/dealer perform this service.
Recommended Actions
Reset the breaker and check for AC voltage at the
generator set side of the circuit breaker.
Move the transfer switch test switch to the AUTO
position.
Check for continuity.
Test and/or replac
e the rotor.
Test and/or replace the stator.†
Tighten loose components.†
Reset the controller. If the overcrank fault occurs again,
contact the distributor/dealer
. †
Verify that the battery connections are correct, clean,
and tight.
Recharge or
replace the battery. The spec sheet
provides recommended battery CCA rating.
Replace the starter or starter solenoid.
Disconnect the engine harness connector(s) then
reconnect it to the controller.
Reset the fault switches and troubleshoot the controller.
Probable Causes
AC output circuit breaker open
.
Transfer switch test switch in the OFF
position
.
Wiring, terminals, or pin in the exciter
field open
.
Main field (rotor) inoperative (open or
grounded)
.
Stator inoperative (open or grounded)
.
Vibration excessive.
Overcrank shutdown.
Battery connections loose, corroded,
or incorrect
.
Battery weak or dead.
Starter/starter solenoid inoperative.
Engine harness con
nector(s) not
locked tight
.
Fault shutdown.
Trouble Symptoms
Exercise run time
and/or event
records
inoperative
Displays error
message/locks up
Excessive or
abnormal noise
X
High fuel
consumption
Low oil pressure
Overheats
Lacks power
Stops suddenly
X
X
No or low output
voltage
X
X
X
X
Starts hard
Cranks but does
not start
X
X
X
X
Does not crank
X
X
X
X
X

Table of Contents

Other manuals for Kohler 12EFKOZD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler 12EFKOZD and is the answer not in the manual?

Kohler 12EFKOZD Specifications

General IconGeneral
BrandKohler
Model12EFKOZD
CategoryPortable Generator
LanguageEnglish

Related product manuals