EasyManua.ls Logo

Kohler 14/20RES - LED Display; Controller Keypad

Kohler 14/20RES
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TP-6734 5/10 19Section 2 Operation
2.5.1 LED Display
When the system is in AUTO and the generator set is not
running, the LED display shows the engine run time
hours. During cranking, the display shows the crank
cycle information.
When the generator is running, the display steps
through the status messages shown in Figure 2-2, as
applicable. The generator set must be connected to a
model RRT transfer switch for the utility voltage display.
When a fault or warning condition exists, the controller
will show the respective message. The following table
shows the various generator conditions and expected
display or messages.
D Generator set is running.
D Model RRT transfer switch is required for utility voltage
display.
D Display steps through the parameters in sequence for
2 seconds each.
tp6734
Engine Runtime
XXX.X or XXXX hours
Utility Voltage
UXXX VAC
Engine Temperature
tXXX
Battery Voltage
bXX.X VDC
Generator Voltage
EXXX VAC
Test or exercise mode,
if applicable.
tnLd, t LD, EnLd, or E Ld
Figure 2-2 Data Displays, Generator Running
Display Description
Blank (dark) Controllerisoff.
u#.# Controller software version number
XXX.X Engine hours to 999.9
XXXX Engine hours, 1000 to 9999
bXX.X Battery voltage
tXX.X Engine temperature
UXXX Utility voltage
EXXX Generator voltage
tnLd Test, no load
tLd Test, loaded
EnLd Exercise, no load
ELd Exercise, loaded
CC1,2,or3 Engine crank cycle 1, 2, or 3. Flashes
during crank pause.
Fault code Warning or fault. See Figure 2-7.
Figure 2-3 RDC Controller Display
2.5.2 Controller Keypad
The Run, Off, Auto, and Down arrow or Exercise buttons
control the generator set as described in Figure 2-4.
See Section 2.6 for operation instructions.
RDC controller only: The Select, Up, and Down
buttons on the controller keypad are used to adjust the
controller parameters. The system configuration and
performance is factory-set and should not require
changes under normal operating conditions. To prevent
inadvertent changes, a pass code is required to access
the controller parameter settings. Contact an
authorized distributor/dealer or service technician if
adjustments are required.

Table of Contents

Related product manuals