General Troubleshooting 4-15TP-5606 6/02
High Defective voltage Test and/or replace Section 7. Voltage
generator regulator Regulator
output
voltage Voltage regulator Readjust Section 7. Voltage
misadjusted Regulator
Open or poor splice Check continuity Section 7. Stator
connection at and clean connections Section 9. Wiring
regulator sensing Diagrams
terminals on stator
or poor pin
connection at
voltage regulator
Problem Possible Cause Corrective Action Reference