EasyManua.ls Logo

Kohler 26RCAL

Kohler 26RCAL
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18 TP-7091 4/23
1.4.2 Exhaust Requirements
Figure 5 gives the exhaust temperature at rated load. The engine exhaust mixes with the generator set cooling air at the exhaust
end of the enclosure. Mount the generator set so that the hot exhaust does not blow on plants or other combustible materials.
Maintain the clearances shown in the dimension drawing.
Exhaust
Temperature, °C (°F)
Exhaust gas exiting the
enclosure at rated kW, °C (°F)
260 (500)
Figure 5 Exhaust Flow and Temperature
The generator set requires correct air flow for cooling and combustion. The inlet and outlet openings in the sound enclosure
provide the cooling and combustion air. Figure 6 shows the locations of the cooling air intake and exhaust vents. Inspect the air
inlet and outlet openings inside and outside the enclosure to ensure that the air flow is not blocked.
Figure 6 Cooling Air Intake and Exhaust
1.5 Dimension Drawings
See the dimension drawings in the Drawings and Diagrams section for the generator set dimensions, fuel and electric inlet
locations, and recommended clearance.
Air intake
Exhaust outlet
Non-Service Side
Air intake
adv8928
14 and 20 kW models
26 kW models
Non-Service Side
Air intake
Air intake
Exhaust outlet
Adv9919

Related product manuals