22 TP-7091 4/23
Fuel Type
% Load
Fuel Consumption, m
3
/hr. (cfh)
14RCA/L
20RCA/L
26RCA/L
60 Hz
60 Hz
60 Hz
Natural
Gas
100%
5.4 (193)
8.0 (281)
8.2 (290)
75%
4.7 (163)
6.9 (243)
6.7 (238)
50%
3.5 (124)
4.6 (161)
5.1 (180)
25%
2.6 (93)
3.6 (127)
3.9 (137)
LPG
100%
2.3 (81)
3.9 (136)
3.6 (129)
75%
2.1 (75)
3.1 (109)
3.1 (111)
50%
1.8 (60)
2.3 (82)
2.4 (85)
25%
1.2 (45)
1.7 (59)
1.8 (64)
LPG conversion factors:
Nominal fuel rating:
8.58 ft.
3
= 1 lb.
Natural gas: 37 MJ/m
3
(1000 Btu/ft.
3
)
0.535 m
3
= 1 kg
LPG: 93 MJ/m
3
(2500 Btu/ft.
3
)
36.39 ft.3 = 1 gal.
Figure 9 Fuel Consumption
2.1.2 Fuel Pipe Size
Ensure that the fuel pipe size and length meet the specifications in Figure 10. Measure the pipe length from the primary gas
pressure regulator to the pipe connection on the generator set fuel inlet. Add 2.4 m (8 ft.) to the measured length for each
90-degree elbow. Compare the total pipe length with the chart in Figure 10 to find the required pipe size.
Contact the local LPG provider for LPG installation information.
Minimum Gas Pipe Size Recommendation, in. NPT
Pipe Length,
m (ft.)
14RCA/L
20RCA/L
26RCA/L
Natural Gas
(193,000
Btu/hr.)
LPG
(203,000
Btu/hr.)
Natural
Gas
(281,000
Btu/hr.)
LPG
(340,000
Btu/hr.)
Natural
Gas
(290,000
Btu/hr.)
LPG
(322,500
Btu/hr.)
8 (25)
¾
¾
1
¾
1
¾
15 (50)
1
¾
1
1
1 ¼
1
30 (100)
1
1
1 ¼
1
1 ¼
1
46 (150)
1 ¼
1
1 ¼
1 ¼
1 ¼
1
61 (200)
1 ¼
1
1 ¼
1 ¼
1 ½
1 ¼
Figure 10 Fuel Pipe Size Recommendations