TP-5985 10/02 5Section 2 Operation
2.6.2 Starting the Generator Set
The following table describes the actions required to
start the generator set.
Explosion.
Gasoline vapors can cause
explosion and severe injury or
death.
Before starting the generator set,
operate the blower 4 minutes and
check the engine compartment for
gasoline vapors.
WARNING
Step
ction
1 Operate the blower.
Operate the blower 4 minutes and check the engine
compartment for gasoline vapors.
2 Fuel shut-off valve.
Open the manual fuel shut-off valve, if equipped.
3 Starting.
Place the generator set controller start/stop switch
or the remote start/stop switch in the START
position.
2.6.3 Remote Panel Gauge Operation
If the generator set has an optional remote panel with
gauges, observe the gauges upon engine start-up. If
gauge readings are not within the ranges specified,
contact an authorized service distributor/dealer.
Gauge Normal Operating Range
Oil pressure 276-414 kPa (40-60 psi)*
W ater temperature
91-104°C (195-219°F)
DC voltmeter 12-14 volts
*50 Hz models show a slightly lower pressure range.
2.6.4 Stopping the Generator Set
The following table describes the actions required to
stop the generator set.
Step
ction
1 Cooldown
Run generator set at no load for 5 minutes to ensure
adequate engine cooldown.
2 Stopping
Place controller start/stop switch or remote
start/stop switch in the stop position and wait until
the generator set comes to a complete stop.
3 Fuel shut-off valve
Close the manual fuel shut-off valve, if equipped.