26 Section 4 Troubleshooting
Section or
Publication
Reference*
Recommended ActionsProbable Causes
Trouble Symptoms
Section or
Publication
Reference*
Recommended ActionsProbable Causes
Excessive or
abnormal noise
High fuel
consumption
Low oil
pressure
Overheats
Lacks power
Stops
suddenly
No or low
output v oltage
Starts hard
Cranks but
does not start
Does not
crank
Fuel System
x x Fuel tank empty or fuel valve shut off Add fuel and move the fuel valve to the ON position.
x x Fuel pressure insufficient (gas only)
Check the fuel supply and valves.[
S/S, Gen. O/M
x x x x Fuel line restriction Check the fuel lines and fuel tank. Eng. O/M
x Antidieseling solenoid inoperative
Replace the solenoid.[
Eng. S/M
x x x Stale or bad fuel. Incorrect type of fuel Replace fuel. Clean the carburetor. Sec. 3, Eng S/M
x x x Fuel feed pump inoperative
Replace the fuel feed pump. [
Eng. S/M
Generator
x
AC output circuit breaker open Reset the breaker and check for AC voltage at the generator
side of the circuit breaker.
x
Transfer switch test switch in the OFF
position
Move the transfer switch test switch to the AUTO position. ATS O/M
x
Wiring, terminals, or pin in the exciter
field open
Check for continuity. Gen. S/M, W/D
x
Main field (rotor) inoperative (open or
grounded)
Test and/or replace the rotor.[
Gen. S/M
x Stator inoperative (open or grounded)
Test and/or replace the stator.[
Gen. S/M
x Vibration excessive
Tighten loose components.[
x x Voltage regulator out of adjustment Adjust the voltage regulator. Gen. S/M
x x
Voltage regulator inoperative Replace the voltage regulator fuse, If the fuse blows again,
troubleshoot the voltage regulator.
Gen. S/M
Lube System
x x x Oil level low Restore the oil level. Inspect the generator set for oil leaks. Eng. O/M
x Low oil pressure shutdown Check the oil level. Eng. O/M
x
Low oil pressure (LOP) switch
inoperative
Replace the LOP switch. W/D
x x x x
Crankcase oil type incorrect for
ambient temperature
Change the oil. Use oil with a viscosity suitable for the operating
climate.
Eng. O/M
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual; S/M—Service Manual;
S/S—Spec Sheet; W/D—Wiring Diagram
[ Have an authorized service distributor/dealer perform this service.