TP-5982 4/06 53Section 8 Reconnection/Adjustments
Parameter Setting Definition Connect
Unit’s system voltage
Single phase, 2W, 60 Hz, 120 VAC 1 Ph, 2W
and frequency *
Uu00
Single phase, 3W, 60 Hz, 120 VAC 1 Ph, 3W
Uu01 Single phase, 3W, 60 Hz, 120/240 VAC 1 Ph, 3W
Single phase, 3W, 50 Hz, 115/230 VAC 1 Ph, 3W
Uu02
Single phase, 2W, 50 Hz, 230 VAC 1 Ph, 2W
Single phase, 2W, 50 Hz, 110 VAC 1 Ph, 2W
Uu05
Single phase, 3W, 50 Hz, 110 VAC 1 Ph, 3W
Single phase, 2W, 50 Hz, 115 VAC 1 Ph, 2W
Uu07 Single phase, 3W, 50 Hz, 110/220 VAC 1 Ph, 3W
Uu08 Single phase, 3W, 60 Hz, 100/200 VAC 1 Ph, 3W
Uu09 Single phase, 3W, 50 Hz, 100/200 VAC 1 Ph, 3W
Uu12 Single phase, 2W, 50 Hz, 220 VAC 1 Ph, 2W
Uu13 Single phase, 2W, 50 Hz, 240 VAC 1 Ph, 2W
Unit configuration Uc00 Marine generator set
Engine type Ec03 10/13/15EG
Ec04 5/7.3ECD and 4/6EFCD
Ec10 [ 13/15EGZ with PTO
Engine data input types
(No magnetic pick-up)
w
Ed00 All digital inputs. Required for 5/7.3ECD and 4/6EFCD.
Default setting for 10/13/15EG and 13/15EGZ with PTO.
Ed01 Digital: Low coolant level and low oil pressure
Analog: Low coolant temperature
Ed02 Digital: Low coolant level and low coolant temperature
Analog: Low oil pressure
Ed03 Digital: Low coolant level
Analog: Low coolant temperature and low oil pressure
Ed08 Digital: Low coolant temperature and low oil pressure
Analog: Low coolant level
Ed09 Digital: Low oil pressure
Analog: Low coolant level and low coolant temperature
Ed10 Digital: Low coolant temperature
Analog: Low coolant level and low oil pressure
Ed11 All analog inputs
Battery Voltage Bt12 Battery voltage 12 VDC
Communications Cn00 No CAN communications
Cn01 SAE J1939 (Used for ADC remote digital gauge)
Cn02 ] SmartCraftt CAN compatible (Required for 5/7.3ECD and 4/6EFCD models)
* Check the generator set spec sheet for voltage configurations applicable to each model.
Use voltage/frequency parameters Uu05--Uu13 only with ADC application program version 1.20 or higher.
[ 13/15EGZ models with PTO require application program version 1.21 or higher.
w Setting the Ec parameter automatically selects the appropriate Ed parameter for the standard data input types for that engine.
Change this parameter if optional senders are installed.
] Smartcraftr settings for ADC code version 2.xx only, for models 5/7.3ECD and 4/6EFCD
SmartCraftt is a trademark of Mercury Marine, a division of Brunswick Corporation.
Figure 8-9 Controller Parameters