6 — COMMISSIONING
Curtis AC F2-A, F4-A, F6-A Motor Controllers – FOS 4.5 – April 2022 Return to TOC
pg. 186
11. In Programmer, under the Tools tab, select the Read Project Values from Device option.
12. In Programmer, under the File tab, save the Project Menu.
13. Email the CIT Project Menu file (.cmnu) and the TACT trace file (.ctrc) to the Curtis
support engineer.
When the test is complete, cycle the keyswitch (KSI) to clear the Parameter Change fault, and then
attempt to drive the motor in the forward direction while monitoring the Motor Speed (the vehicle is
still on the blocks). If the motor speed shows a negative value, invert the Swap Direction parameter
in the Commissioning Tests menu (note, there is no swap two phases parameter like the induction
motor control – swap direction takes care of both).
e test data les (emailed to Curtis) will determine the nal PMAC commissioning.