TP-6694 2/25 27
Current L3
The user can change individual values or can enter Yes when Reset all Calib? is displayed. At the end of the Generator Set
Calibration menu, Exit calibration is shown. Press the pushbutton/rotary selector dial to exit this menu. Refer to the requirements
shown with Generator Set Calibration in the section titled: Status and Notice Digital Displays.
Voltage Regulator Menu
Decision-Maker
®
3000 Controller firmware before 3.0.25:
The voltage regulator value is reviewable at all times. In order to review the value when the generator set is NOT running, enter
Yes when the Enter volt reg? is displayed. The user can review the value but attempting to change the value will cause a Cannot
edit when stopped error message.
If the unit is NOT running and No is entered when the Enter volt reg? is shown, the display returns to the Voltage Regulator main
menu and entry to the Voltage Regulator menu is denied.
If the unit is running and Yes is entered when the Enter volt reg? is shown, the display will show the value.
The user can change the value at this time. At the end of the Voltage Regulator menu, Exit voltage reg is shown- - press the
pushbutton/rotary selector dial to exit this menu.
Decision-Maker
®
3000 Controller firmware 3.0.25 and higher, or APM402 Controller:
The voltage regulator value is reviewable at all times and provides the ability to fine adjust voltage. Changing the system voltage
or replacing the circuit board typically requires a voltage adjustment.
To enable calibration, start the generator set and select the VR Volt Adj display. Then push and hold the pushbutton/rotary
selector dial until the Editing Enabled popup appears. Editing of the voltage adjustment is now available.
The user can change the individual value or can select Reset VR?- Yes to reset to the default value. The Reset VR Settings
display will only show if editing is enabled.
To disable calibration, Rotate the pushbutton/rotary selector dial until the <- Return popup appears. Momentarily press the
pushbutton/rotary selector dial. Stop the generator set if not already done.
Digital Inputs Menu
This menu allows the user to review the settings. There are up to three digital inputs that are programmer selectable if not
reserved by factory options.
The displays for digital inputs appear as shown below with Values true or false. Items shown in the digital display as True are
active.
DIn A1 (digital input A1) standard
DIn A2 (digital input A2) standard
DIn A3 (digital input A3) standard (see note below)
DIn B1 (digital input B1) with I/O module board
DIn B2 (digital input B2) with I/O module board
Changes to the Digital Inputs menu requires the use of SiteTech software. The digital input can either open or close the circuit
to activate.
Note:
DIn A3 digital input is factory reserved for Enclosure Temperature: High Shutdown on select Telecom units.
Note:
DIn A2 digital input is factory reserved for wait to start software on select diesel generators.
Digital Outputs Menu
This menu allows the user to review the settings. There is one digital output standard with the controller that is programmer
selectable. The one SPDT switch has 2 amps. contacts at 32 VDC or 0.5 amp. contacts at 120 VAC max.
There is an optional 2 input/5 output (I/O) module board available that can provide five digital outputs. The standard digital output
on the controller is used to drive the optional I/O Module board and becomes factory reserved and no longer available as
programmer selectable.