28 TP-6694 2/25
The displays for digital outputs appear as shown in the following list with Values as True or False. Items shown in the digital
display as True are active.
• DOut A1 (digital output A1) standard
• DOut B1 (digital output B1) with I/O module board
• DOut B2 (digital output B2) with I/O module board
• DOut B3 (digital output B3) with I/O module board
• DOut B4 (digital output B4) with I/O module board
• DOut B5 (digital output B5) with I/O module board
Changes to the Digital Outputs menu requires the use of SiteTech™ software. The digital output can either open or close the
circuit to activate.
Analog Inputs Menu
This menu allows the user to review the settings. There is one analog input that is programmer selectable if not reserved by
factory options.
There is an optional 2 input/5 output (I/O) module board available that can provide two additional analog inputs.
The displays for analog inputs appear as shown below with Values of 0-5 volts.
• AIn A1 (analog input A1) standard (reserved and not user programmable)
• AIn A2 (analog input A2) standard
• AIn B1 (analog input B1) with I/O module board
• AIn B2 (analog input B2) with I/O module board
Changes to the Analog Inputs menu requires the use of SiteTech™ software.
Event Log Menu
This menu allows the user to review up to 1000 entries of system events including shutdown faults, warning faults, and status
events. See the section titled: Controller Fault Diagnostics for a list of the items that appear on the Event Log.
Volt Select Menu
Note:
The generator set must be stopped before changing the voltage selection.
This menu allows the user to readily change controller voltage settings. The volt select feature is typically used in towable or
temporary applications.
Note:
The volt select menu requires initial activation by SiteTech™ software. In SiteTech™ software, select True to activate the volt
select menu.
Note:
The generator set output leads require voltage reconnection if the generator set does not have a voltage selector switch installed.
With the generator set stopped, go to the Volt Select menu. Then push and hold the pushbutton/rotary selector dial until the
voltage selection starts to flash. Volt selection is now available. Scroll to the desired voltage and momentarily press the
pushbutton/rotary selector dial to confirm the voltage selection.
The displays for Volt Select appear as shown in the following list.
• 120/240 V 1 Ph
• 120/208 V 3 Ph
• 139/240 V 3 Ph
• 277/480 V 3 Ph
• 120/240 V 3 Ph