TP-6694 2/25 55
Figure 18 SW Version Submenu
7. For Decision-Maker
®
3000 controllers, if the firmware version is earlier than 3.10, go to the Procedure for Powering Up
the Engine ECM using SiteTech™. For Decision-Maker
®
3000 controllers with firmware version 3.10 or higher, or for
APM402 controllers, continue to Procedure for Powering Up the Engine ECM.
Procedure for Powering Up the Engine ECM
This procedure applies to Decision-Maker
®
3000 controllers with firmware version 3.10 and higher and to APM402 controllers
with firmware versions 1.0 and higher.
1. Navigate to the SW Version menu (Figure 19) as described in the previous procedure. Press and hold the selector dial
until the display screen confirms that the ECM is powered as shown in Figure 20.
Figure 19 SW Version Submenu
Figure 20 ECM Powered Display
2. After several seconds, the display will change to provide the option to power down the controller. See Figure 21.
Figure 21 ECM Power Down Display
3. If desired, press the selector dial to power down the engine ECM.
OR
Rotate the selector dial to navigate to any of the available menus.
Procedure for Powering Up the Engine ECM using SiteTech™ (for Decision-Maker
®
3000 controllers with Firmware
Versions Before 3.10)
Connect a PC with SiteTech™ software to the generator set controller. Refer to the SiteTech™ Software Operation Manual
TP-6701 as needed.
Follow the instructions shown in Figure 22.