TP-6694 2/25 93
For KG40 and KG50 (Kohler Engine KG04V06T), use the following:
See Figure 41.
Natural Gas Operation
• Disconnect N4 and FS
• Connect 70NG1 and N16 to FV1
• Connect 70NG2 and NG to FV3
LPG Vapor Operation
• Connect N4 and FS
• Connect 70LP1 and N28 to FV2
• Connect 70LP2 and LP to FV3
Figure 41 Gaseous Fuel Connections Wiring Diagram, KG40 and KG50 (KG04V06T)
For KG40 and KG50 (Kohler Engine KG04V06T) Dual Fuel Connections
Automatic changeover dual fuel systems are factory connected. No changes to the electrical connections for a dual fuel system
are required in the field. The connections are shown in the connection diagrams for reference.
Figure 42 Gaseous Fuel Connections Wiring Diagram, KG40 and KG50 (KG04V06T) Dual Fuel