TP-6881 7/1536 Section 3 Controller
SiteTech Group Notes [
Default
Setting
Adjustment
Range *
UnitsParameter
Genset System
Configuration
Prime Power Application Standby or prime Standby
Genset System
Configuration
Current Transformer Ratio Locked 400 N/A
Genset System
Configuration
Local Start Mode Read Only Off
Genset System
Configuration
Measurement System English or metric English
Genset System
Configuration
ECM Power On or Off Off
Genset System
Configuration
Display Contrast 0 -- 100 50
Genset System
Configuration
Genset System Language 0--4 English N/A
Genset System
Configuration
Genset Maximum Percent
Capacity
% 0 -- 120 70.0
Genset System
Configuration
Generator Overloaded Percent % 0 -- 120 85.0
Genset System
Configuration
Under Frequency Shed Level Hz 0--5 0.5
Genset System
Configuration
Base Load Add Time s 10 -- 2400 60
Genset System
Configuration
Base Over Load Shed Time s 2--30 30
Genset System
Configuration
Base Under Frequency Shed
Time
s 1--20 5
Genset System
Configuration
Genset Fuel Type Natural Gas or LPG
(pulldown)
Natural Gas
Genset System
Configuration
Automatic Start Minimum
Voltage
V 15 -- 60 51
Genset System
Configuration
Automatic Stop Minimum
Percent Load
% 0 -- 100 20
Genset System
Configuration
Automatic Start Minimum
Voltage Delay
s 1 -- 3600 180
Genset System
Configuration
Automatic Stop Minimum Load
Delay
s 1 -- 3600 180
Genset System
Configuration
ECM Powered Mode On or Off Off
Genset Calibration Genset Calibration Factor
Voltage L1-L2
0.9 -- 1.1 0.9803
Genset Calibration Genset Calibration Factor
Voltage L2-L3
0.9 -- 1.1 0.98600
Genset Calibration Genset Calibration Factor
Voltage L3-L1
0.9 -- 1.1 0.9900
Genset Calibration Genset Calibration Factor
Current L1 -- N
0.9 -- 1.1 1.000000
Genset Calibration Genset Calibration Factor
Current L1
0.9 -- 1.1 1.04
Genset Calibration Genset Calibration Factor
Current L2
0.9 -- 1.1 1.04
* Read Only = Not adjustable
w Load management device (LCM, load shed kit, or RXT w ith c ombined interface/ load management board).
[ Notes indicate applicability to genset or accessories. N/A = Not applicable to the models covered in this manual.
] See TT-1584 for more information about digital inputs and outputs.
Grayed rows are visible in SiteTech but do not apply to all models.