EasyManuals Logo

Kohler Power Systems 8RESV User Manual

Kohler Power Systems 8RESV
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
TP-6881 7/15 37Section 3 Controller
SiteTech Group Notes [
Default
Setting
Adjustment
Range *
UnitsParameter
Genset Calibration Genset Calibration Factor
Current L3
0.9 -- 1.1 1.04
Genset Calibration Current Transformer Calibration
At No Load
0 -- 100 3.5
Genset Calibration Current Transformer Calibration
At Full Load
0 -- 400 121.5
Advanced Speed Control Proportional Gain No effect. N/A
Advanced Speed Control Transient Integral Gain No effect. N/A
Advanced Speed Control Derivative Gain No effect. N/A
Advanced Speed Control Slow Correction Integral Gain No effect. N/A
Advanced Speed Control Diagnostic Derivative Gain No effect. N/A
Advanced Speed Control Diagnostic Transient Integral
Gain
No effect. N/A
Voltage Regulator Voltage Regulator Average
Voltage Adjustment
V 108 -- 660 240.0
(System
voltage)
Voltage Regulator Voltage Regulator Volts Per
Hertz Slope
% 1-- 10 5
Voltage Regulator Voltage Regulator Volts Per
Hertz Cut In Frequency
Hz 42 -- 62 59
Voltage Regulator Voltage Regulator Gain 1 -- 255 16
Engine Timing Engine Start Delay s 0 -- 300 0
Engine Timing Engine Cool Down Delay s 300 -- 600 300
Engine Timing Engine Crank On Delay s 10 -- 30 15
Engine Timing Engine Crank Pause Delay s 1--60 15
Engine Timing Engine Number Of Crank
Cycles
1--6 3
Genset Protection Genset Low Battery Voltage
Warning Delay
s Read Only 90
Genset Protection Genset High Battery Voltage
Warning Delay
s Read Only 10
Genset Protection Genset Low Battery Voltage
Warning Limit
% 80 -- 100 100
Genset Protection Genset High Battery Voltage
Warning Limit
% 110 -- 135 125
Genset Protection Genset Battery Low Cranking
Voltage Warning Delay
s Read Only 6
Genset Protection Genset Battery Low Cranking
Voltage Warning Limit
% Read Only 60
Engine Protection Engine Locked Rotor Shutdown
Delay
s 1--5 3
Engine Protection Genset Low Engine Speed
Shutdown Limit
% 75 -- 95 85
Engine Protection Genset High Engine Speed
Shutdown Limit
% No effect. N/A
Engine Protection Engine Low Oil Pressure
Warning Limit
kPa No effect. N/A
Engine Protection Engine High Oil Pressure
Shutdown Limit
kPa No effect. N/A
* Read Only = Not adjustable
w Load management device (LCM, load shed kit, or RXT w ith c ombined interface/ load management board).
[ Notes indicate applicability to genset or accessories. N/A = Not applicable to the models covered in this manual.
] See TT-1584 for more information about digital inputs and outputs.
Grayed rows are visible in SiteTech but do not apply to all models.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler Power Systems 8RESV and is the answer not in the manual?

Kohler Power Systems 8RESV Specifications

General IconGeneral
BrandKohler
ModelPower Systems 8RESV
CategoryPortable Generator
LanguageEnglish

Related product manuals