TP-6881 7/1538 Section 3 Controller
SiteTech Group Notes [
Default
Setting
Adjustment
Range *
UnitsParameter
Generator Protection Loss Of AC Sensing Shutdown
Delay
s Read Only 3
Generator Protection Genset Low Voltage Shutdown
Delay
s Read Only 10
Generator Protection Genset High Voltage Shutdown
Delay
s Read Only 2
Generator Protection Genset Low Voltage Shutdown
Limit
% Read Only 80
Generator Protection Genset High Voltage Shutdown
Limit
% Read Only 120
Generator Protection Genset Short Term Low
Frequency Shutdown Delay
s Read Only 10
Generator Protection Genset Long Term Low
Frequency Shutdown Delay
s Read Only 60
Generator Protection Genset High Frequency
Shutdown Delay
s Read Only 10
Generator Protection Genset Low Frequency
Shutdown Limit
% Read Only 90
Generator Protection Genset High Frequency
Shutdown Limit
% Read Only 110
Digital Input A1 Digital Input A1 Value Read Only False N/A
Digital Input A1 Digital Input A1 Enabled True or False True N/A
Digital Input A1 Digital Input A1 Event See dropdown list in
SiteTech.
]
Fuel
Pressure
Low
Warning
N/A
Digital Input A2 Digital Input A2 Value Read Only False N/A
Digital Input A2 Digital Input A2 Enabled True or False True N/A
Digital Input A2 Digital Input A2 Event See dropdown list in
SiteTech.
]
Auxiliary
Input
Warning
N/A
Digital Input B1 Digital Input B1 Value Read Only False PIM
Digital Input B1 Digital Input B1 Enabled True or False False PIM
Digital Input B1 Digital Input B1 Event See dropdown list in
SiteTech.
]
None (0) PIM
Digital Input B2 Digital Input B2 Value Read Only False PIM
Digital Input B2 Digital Input B2 Enabled True or False False PIM
Digital Input B2 Digital Input B2 Event See dropdown list in
SiteTech.
]
None (0) PIM
Digital Output A1 Digital Output A1 Value Read Only False N/A
Digital Output A1 Digital Output A1 Event See dropdown list in
SiteTech.
]
NFPA 110
Alarm Active
N/A
Digital Output A2 Digital Output A2 Value Read Only N/A N/A
Digital Output A2 Digital Output A2 Event See dropdown list in
SiteTech.
]
N/A N/A
Digital Output B1 Digital Output B1 Value Read Only False PIM
Digital Output B1 Digital Output B1 Event See dropdown list in
SiteTech.
]
Generator
Running
PIM
Digital Output B2 Digital Output B2 Value Read Only False PIM
* Read Only = Not adjustable
w Load management device (LCM, load shed kit, or RXT w ith c ombined interface/ load management board).
[ Notes indicate applicability to genset or accessories. N/A = Not applicable to the models covered in this manual.
] See TT-1584 for more information about digital inputs and outputs.
Grayed rows are visible in SiteTech but do not apply to all models.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler Power Systems 8RESV and is the answer not in the manual?

Kohler Power Systems 8RESV Specifications

General IconGeneral
BrandKohler
ModelPower Systems 8RESV
CategoryPortable Generator
LanguageEnglish

Related product manuals