TP-5631 7/96 Generator Reconnection 5-3
100-120/200-240 Volt
Jumperleadnotused. Ifthegeneratorsetwasoriginally
wiredfor straight100-120volt 3wire, besure toremove
jumperlead. SeeFigure 5-4forlocationof jumperlead.
LeadsL1andL2areofdifferentphases. Neverconnect
Leads L1 and L2 together.
NOTE
Use a circuit breaker manufacturer’s two-pole circuit
breaker. Two single-pole circuit breakers do not
conform to NEC requirements when supplying a
200-240 volt load. This is true even if they are
mechanically attached together.
L0-L1
L0-L2
L1-L2
6
0
H
z
100-120 volt
100-120 volt
2
0
0
-
2
4
0
v
o
l
t
5
0
H
z
100-120 volt
100-120 volt
2
0
0
-
2
4
0
v
o
l
t
4 3 2 1
Stator Leads
LO
GRD
L2
L1
LO (Neutral)
Line
Side
Factory
Two-Pole
Circuit
Breaker
Ground
Load
Side
TP-5631-5
UP V7 LO
TB2
Meter Scale
Lamp Jumper
CT1
CT2
Figure 5-4. 100-120/200-240 volt, 3 wire
configurations
200-240 Volt
Jumperleadnotused. Ifthegeneratorsetwasoriginally
wiredforstraight100-120volt, 3wire,besuretoremove
jumperlead. SeeFigure 5-5forlocationof jumperlead.
4 3 2 1
Stator Leads
LO
GRD
L1
LO (Neutral)
Line
Side
Single-Pole
Circuit
Breaker
Ground
Load
Side
Tape to insulate
from ground
TP-5631-5
UP V7 LO
TB2
Meter Scale
Lamp Jumper
CT2 not used
CT1
Figure 5-5. 200-240 volt, 2 wire configurations