3
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
CAPACITY DATA
Cooling Capacity (A)
Heating Capacity (B) & (D)
Evaporator-CFM @ 0.0 ESP
ELECTRICAL DATA
Volts (Single Phase)
Amperes (Cooling)
Amperes (Heating)
Watts (Cooling)
Watts (Heating)
E.E.R.
C.O.P.
Fuse/Breaker amps
Compressor H.P.
Blower Motor H.P.
In Rush Current (amps)
CONDENSATE PUMP
Motor H.P.
RPM
Voltage
Amperage Draw
Lift (Feet of H
2
O)
CONDENSER WATER FLOW & PRESSURE DROP DATA (G)
GPM @ 85° F L.W.T.
Cond. Coil ∆P (P.S.I)
Water Valve ∆P (P.S.I)
GPM @ 60° F E.W.T. 100° F L.W.T.
Cond. Coil ∆P (P.S.I.)
Water Valve ∆P (P.S.I.)
Max. Water Side Working Pressure/With Water Valve-150 P.S.I./Without Valve-400 P.S.I.
MISC. DATA
Evap. Coil-# of Rows
Coil Face Area (FT2)
Refrigerant Charge R-22 in oz.
Water Connections
DIMENSIONAL DATA (inches)
(A) Height-With Casters
(B) Height-Without Casters
(C) Length
(D) Depth
AIR FILTER DATA (inches)
Width
Height
Thickness
NET WEIGHT
SHIPPING WEIGHT
PRODUCT SPECIFICATIONS FOR KOMPAC SERIES
2K07DB
2K07DBH
7,000
7,800
250
115
8.00
7.50
897
840
7.80
2.70
15
1
/2
1
/25
45.20
1
/80
3,000
115
0.48
11.00
1.75
1.40
2.00
0.44
0.60
2.00
3
0.83
14
3
/8″ MF
16
5
/8
16
1
/8
22
3
/8
12
15
3
/4
9
1
/4
1
/2
83
89
2K10DB
2K10DHB
9,400
10,900
345
115*
9.8
9.50
1,000
1,065
9.40
3.00
15
3
/4
1
/15
71.50
1
/80
3,000
115*
0.48
11.00
2.25
1.70
2.00
0.56
0.70
2.00
3
1.05
18
3
/8″ MF
31
1
/2
29
1
/8
25
10
3
/16
18
16
1
/2
123
132
2K14DB
2K14DHB
12,500
14,200
410
115*
11.60
10.80
1,276
1,301
9.80
3.20
15
1
1
/15
71.50
1
/80
3,000
115*
0.48
11.00
3.00
3.00
3.00
0.75
0.80
2.00
3
1.20
20
3
/8″ MF
31
1
/2
29
1
/8
25
10
3
/16
18
16
1
/2
124
133
2K16DB
2K16DHB
16,000
17,900
480
115*
13.00
13.00
1,684
1,692
9.50
3.10
20
1
1
/4
1
/15
96.50
1
/80
3,000
115*
0.48
11.00
4.00
5.30
5.00
1.00
1.00
2.00
3
1.20
22
3
/8″ MF
31
1
/2
29
1
/8
25
10
3
/16
18
16
1
/2
125
134
2K20DB
2K20DHB
20,500
24,000
650
208/230
10.40/10.10
10.50/10.10
2,092
2,269
9.80
3.10
15
1
1
/2
1
/7
61.90
1
/77
3,000
208/230
0.26
11.00
4.50
4.20
8.00
1.10
0.50
2.00
3
1.90
26
3
/8″ MF
28
3
/4
26
3
/8
36
12
1
/4
24
11
3
/4
1
/2
175
191
2K26DB
2K26DHB
26,000
31,000
800
208/230
12.70/11.80
12.50/11.50
2,708
2,839
9.60
3.20
20
2
1
/7
72.90
1
/77
3,000
208/230
0.26
11.00
6.00
6.80
14.00
1.50
0.80
2.00
4
1.90
30
3
/8″ MF
28
3
/4
26
3
/8
36
12
1
/4
24
11
3
/4
1
/2
183
201
2K26DBL
2K26DHBL
23,200
31,000
800
208/230
12.70/11.80
12.50/11.50
2,416
2,839
9.60
3.20
20
2
1
/7
72.90
1
/77
3,000
208/230
0.26
11.00
6.00
6.80
14.00
1.50
0.80
2.00
4
1.90
30
3
/8″ MF
28
3
/4
26
3
/8
36
12
1
/4
24
11
3
/4
1
/2
183
201
(A) Cooling Capacity Rating Test Conditions: Evaporator Air - 80°F D.B./67°F W.B.
Condenser Water - 85°F E.W.T./95°F L.W.T.
(B) Heating Capacity Rating Test Conditions: Condenser Air - 70°F D.B./60°F W.B
Evaporator Water - 70°F E.W.T.
(C) Time Delay Fuses and Circuit Breakers are recommended.
(D) Reverse cycle units require 50°F minimum water inlet temperature during the heating cycle.
(E) Total pressure drop for unit with Water Regulating Valve is sum of Condenser Coil and Water Valve Pressure Drop.
*Also available in 208/230 volt.