1. INSTALLATION MANUAL
Installationworkscanbeperformedonlybythespecialiststhathaverequiredqualication.Duringinstallation
followingrequirementsmustbefullled.
It is recommended to lay control cables separately from power cables in a distance
no less than 20 cm.
1.1. Electric Power Supply Connection
Air handling unit voltage is 230V AC; 50 Hz , therefore it is necessary to install the socket with grounding of
corresponding capacity (see wiring diagram). Electric power supply cable type is indicated in electric diagram.
Unit must be connected to the stationary installation by solid cable through 10A
circuit breaker with maximum 30mA current leakage relay.
Before connecting unit to the electrical power supply, it is necessary to check
whether earthing has been installed properly in conformance with electric safety
requirements.
1.2. Control Panel Installation
1. Control panel must be installed in the room under given following conditions:
•ambienttemperature0
0
C ... 40
0
C;
•relativehumiditylimits20%...80%;
•protectionmustbeensuredfromaccidentallyverticallyfallingwaterdrops(IPX2).
2. Installation height must be not less than 0,6m from the ground.
3. Control panel connection is projected through the hole in its backside (see 1.2 Picture).
4.Controlpanelisxedafterscrewingtwoholesonthefasteningsurface.
1.2 Picture
Control Panel Connection
The length of cable connecting control panel and air handing unit can not exceed
20 m. Electric power supply cable type is indicated in wiring diagram.
Installation Manual