EasyManua.ls Logo

KROHNE SU 600 Ex - User Manual

KROHNE SU 600 Ex
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Operating Instructions
SU 600 Ex
4 … 20 mA signal conditioning instrument
Document
ID: 30653
Question and Answer IconNeed help?

Do you have a question about the KROHNE SU 600 Ex and is the answer not in the manual?

Overview

The KROHNE SU 600 Ex is a universal signal conditioning instrument and power supply unit designed for connection of a 4...20 mA/HART sensor. It is suitable for use in explosion-endangered areas, being an intrinsically safe instrument. The device provides continuous sensors with integrated level switches and a display for continuous sensors. It can serve as a power supply unit for the connected sensor and is designed for connection to any 4...20 mA sensor. The instrument is suitable for carrier rail, panel, and surface mounting.

Function Description

The SU 600 Ex signal conditioning instrument processes and displays measurement signals from connected sensors. It converts the measured variable into a remote indication or a superior-directing control system. The device features two level relays for control of pumps or other devices. The instrument is operated via integrated keys and a 16-step function switch.

The device offers various functionalities, including:

  • Measurement data input: The instrument receives measurement data from a sensor via a 4...20 mA signal.
  • Current output: Provides a 4...20 mA current output.
  • Fail-safe relay: Includes a fail-safe relay for enhanced safety.
  • Relay 1 and Relay 2: Two relays are available for switching operations.
  • Voltage supply: Supplies power to the connected sensor.

The SU 600 Ex can operate in two modes:

  • Active mode: The SU 600 Ex provides power for the connected sensors. Power supply and measurement data are transmitted over the same two-wire cable. This mode is suitable for connection of measuring transducers without separate voltage supply (sensors in two-wire version).
  • Passive mode: The sensors are not powered by the SU 600 Ex. The measurement value is transmitted. This input is for connection of transmitters with their own separate voltage supply (sensors in four-wire version). The SU 600 Ex can also be looped into the existing circuit like a normal ammeter.

The instrument features an integrated display and adjustment unit. The LC display shows the measured value, adjustment, and diagnosis. A function switch and two keys are used for operation.

Important Technical Specifications

General Data:

  • Series: Instrument for mounting into front panel, switching cabinet or housing
  • Weight: 400 g (0.882 lbs)
  • Housing material: plastic ABS/POM
  • Connection terminals: Screw terminal
  • Max. wire cross-section: 1.5 mm² (AWG 16)

Voltage Supply:

  • Operating voltage: 20...253 V AC, 50/60 Hz, 20...253 V DC
  • Max. power consumption: 12.4 VA, 4 W

Sensor Input:

  • Number of sensors: 1 x 4...20 mA
  • Type of input (switchable):
    • Mode active: Sensor is powered by SU 600 Ex
    • Mode passive: Sensor has an own power supply
  • Measured value transmission: 4...20 mA
  • Deviation: ±20 µA (0.1 % of 20 mA)
  • Terminal voltage mode active: 20...15 V at 4...20 mA
  • Current limitation mode active: 30 mA
  • Internal resistance mode passive: < 250 Ω
  • Detection line break: ≤ 3.6 mA
  • Detection shortcircuit: ≥ 21 mA
  • Adjustment range:
    • Empty adjustment: 3.8...20.2 mA
    • Full adjustment: 4.1...20.5 mA
    • Min. adjustment delta: 300 µA
  • Connection cable to the sensor: two-wire standard cable (screening recommended)

Relay Outputs:

  • Quantity: 2 x operating relay, 1 x fail safe relay
  • Contact: Floating spdt
  • Contact material: AG Ni 0.15 hard gold-plated
  • Switching voltage: min. 10 mV DC, max. 250 V AC/DC
  • Switching current: min. 10 µA DC, max. 3 A AC, 1 A DC
  • Breaking capacity: min. 50 mW, max. 500 VA, max. 54 W DC
  • Min. switching hysteresis: 0.5 %

Current Output:

  • Quantity: 1 x output
  • Range: 0/4...20 mA
  • Resolution: 0.1 %/20 µA
  • Max. load: 500 Ω
  • Fault message: 22 mA
  • Accuracy: ±25 µA (0.125 % of 20 mA)
  • Temperature error (relating to 20 mA): 0.01 %/K

Indicators:

  • Measured value indication: digital and quasianalogue indication
  • Max. indicating range: -9999...9999
  • LED displays:
    • Status, operating voltage: 1 x LED green
    • Status, fault signal: 1 x LED red
    • Status operating relay 1/2: 2 x LED yellow

Ambient Conditions:

  • Ambient temperature: -20...+60 °C (-4...+140 °F)
  • Storage and transport temperature: -40...+80 °C (-40...+176 °F)

Electrical Protective Measures:

  • Protection rating:
    • Wall, rail mounting: IP 20
    • Front panel mounting: IP 40
  • Overvoltage category: II
  • Protection class: II

Electrical Separating Measures:

  • Reliable separation according to VDE 0106 part 1 between power supply, sensor input and digital component:
    • Reference voltage: 250 V
    • Voltage resistance of the isolation: 3.75 kV
  • Galvanic separation between relay output and digital part:
    • Reference voltage: 250 V
    • Voltage resistance of the isolation: 4 kV

Dimensions:

  • Width: 69 mm (2.72")
  • Height: 96 mm (3.78")
  • Depth: 111 mm (4.37")
  • Panel cutout: 92 x 92 mm (3.63 x 3.63 in)

Usage Features

Mounting: The SU 600 Ex is designed for recessed installation in a front panel, housing front plate or a switching cabinet door. It requires a cutout of 92 x 92 mm (3.63 x 3.63 in). The protection rating IP 40 is guaranteed when installed correctly. The instrument can be mounted into a switching cabinet or housing by means of three screws (fixed with screws on rear of housing). A mounting adapter for carrier rail mounting is optionally available.

  • Front panel mounting:

    1. Make sure that the cutout required for installation has a size of 92 x 92 mm (3.63 x 3.63 in). The required installation depth is min. 90 mm (3.54 in).
    2. Remove the pluggable terminal strips from the top and bottom.
    3. Screw the threaded pin into the rear of the instrument and tighten with a screwdriver.
    4. Insert the instrument from the front into the front panel.
    5. Place the clamping strap from the back over the pin and push the instrument upward until it snaps in.
  • Screw mounting:

    1. Insert the metal strap from above into the housing cut-out.
    2. Fasten the instrument directly to the wall with three screws (max. ø 4 mm).
  • Carrier rail mounting:

    1. Place the adapter plate onto the rear of SU 600 Ex (spring of the adapter plate downward) and fasten the plate with screw.
    2. Place SU 600 Ex against the carrier rail from below and push the instrument upward until it snaps in.

Connecting to Power Supply: The SU 600 Ex is connected using standard two-wire cable without screen. Electromagnetic interference is expected which is above the test values of EN 61326 for industrial areas, screened cable should be used. The cable screen must be connected directly to the internal ground terminal. The ground terminal cable on the sensor housing must be connected to the potential equalisation.

Setup and Adjustment: The integrated display and adjustment unit is used for measured value display, adjustment, and diagnosis. The LC display and the adaptation of the relay switching points are further settings. Additional setup steps would be, if necessary, setting an integration time (damping) to steady the measured value or modifying the current output characteristics.

  • Switch-on phase: After being switched on, the SU 600 Ex carries out a self-check. The following steps are carried out:

    • Internal check of the electronics
    • Indication of the firmware version
    • The output signal jumps briefly to the set fault value
    • The actual measured value is displayed and the corresponding current is transmitted to the current output.
  • Measured value indication: The measured value indication shows the digital indication value and also an analogue bargraph. The function switch is set to position 0 ("OPERATE").

  • Function switch: The following functions can be selected via the rotary switch:

    • Measured value display and simulation
    • Relay 1 switching point ON/OFF
    • Relay 2 switching point ON/OFF
    • Decimal point position of the scaling
    • Scaling for 100 %
    • Scaling for 0 %
    • Switch over current output 0/4...20 mA
    • Damping of the measured value (integration time)
    • Offset correction
    • Min. adjustment in percent through change of the level
    • Max. adjustment in percent through change of the level
    • Min. adjustment in mA without changing the level
    • Max. adjustment in mA without changing the level
    • No function
  • Offset correction: When a pressure transmitter is used, an offset correction should be carried out first. These instruments are factory-set in a certain position. If the pressure transmitter is now mounted in a different position, its measuring range is shifted slightly. The zero point is readjusted by carrying out the offset correction in uncovered (unpressurised) conditions.

  • Adjustment in mA without changing the level: For this adjustment procedure, two sensor current values (4...20 mA) must be entered corresponding to the levels 0 % and 100 %.

  • Adjustment in % by changing the level: During this adjustment procedure, the current level is assigned to a certain percentage value. For this reason, percentage values that correspond to the actual filling levels must be entered for the min. and max. adjustment. The ideal calibration is at 0 % and 100 %. Because it is not always possible to empty or fill a vessel completely, any value can of course be entered. The greater the difference between the two adjustment points, the more precise the measurement. It does not matter which value is entered first.

  • Relay outputs: Two operating relays are integrated. The relays should switch on and off again. If there are two relays, you have to distinguish between the relay modes overfill and dry run protection. You switch over by exchanging the ON/OFF values of the relay.

    • Overflow protection: Relay is switched off when the max. level is exceeded (safe currentless state), relay is switched on again when the level falls below the min. level (switch-on point < switch-off point).
    • Dry run protection: Relay is switched off when the level falls below the min. level (safe currentless state), relay is switched on again when the max. level is exceeded (switch-on point > switch-off point).
  • Scaling: Scaling means converting the measured value into a certain parameter and unit. The indication can then show the volume in litres, instead of the percentage value. Indication values from -9999 to +9999 are possible.

  • Damping: To suppress fluctuations in the measured value display, e.g. caused by an agitated product surface, an integration time can be set. The time can be between 0 and 250 seconds. Remember that the reaction time of the entire measurement will then be longer and the sensor will react to measured value changes with a delay.

  • Current output 0/4...20 mA: The characteristics of the current output can be switched over from 4...20 mA to 0...20 mA.

  • Simulation: The settings of SU 600 Ex are correct, the simulation mode can be used. Any individual measured value can be simulated and e.g. the correct behaviour of the relays and the connected instruments can be checked.

  • Reset: With a reset, all values set by the user will be lost and are reset to factory settings.

Maintenance Features

Maintenance: If the instrument is used properly, no special maintenance is required in normal operation.

Rectify Faults: The operator of the system is responsible for taking suitable measures to rectify faults. Maximum reliability is ensured. Nevertheless, faults can occur during operation. These may be caused by:

  • Measured value from sensor not correct
  • Voltage supply
  • Interference in the cables

The first measures to be taken are to check the input/output signals as well as to evaluate the error messages via the display. The procedure is described below. In many cases, the causes can be determined in this way and faults can be rectified.

Fault message: The signal conditioning instrument and the connected sensors are permanently monitored during operation and the values entered during parameter adjustment are checked for plausibility. If irregularities occur or in case of incorrect parameter adjustment, a fault signal is triggered. In case of an instrument defect or line break/shortcircuit, a fault signal is also triggered. The fail safe relay deenergises in case of failure, the failure indication lights and the current output jumps to 22 mA. In addition, one of the following fault messages is outputted on the display.

Error code Cause Rectification
E003 CRC error (error with self-check) – Carry out a reset
– Send instrument for repair
E014 Sensor current > 21 mA or short-circuit – Check sensor, e.g. on failure
– Remove short-circuit
E015 Sensor in boot phase
Sensor current < 3.6 mA or line break
– Check sensor, e.g. on failure
– Remove line break
– Check connection of the sensor
E016 Empty/full adjustment reversed – Carry out a fresh adjustment
E017 Adjustment span too small – Carry out a fresh adjustment and increase the distance between min. and max. adjustment
E21 Scaling span too small – Carry out a fresh scaling, increase the distance between min. and max. scaling.
E110 Relay switching points too close together – Increase the difference between the two relay switching points

Instrument repair: If a repair is necessary, please proceed as follows:

  • On our homepage in the Internet under http://www.krohne-mar.com/fileadmin/media-lounge/PDF-Download/Specimen_e.pdf you can download a return form.
  • By doing this you help us carry out the repair quickly and without having to call back for needed information.
  • Print and fill out one form per instrument
  • Clean the instrument and pack it damage-proof
  • Attach the completed form and possibly also a safety data sheet to the instrument

Disposal: The instrument consists of materials which can be recycled by specialised recycling companies. We use recyclable materials and have designed the parts to be easily separable. This instrument is not subject to the WEEE directive 2002/96/EG and the respective national laws. Pass the instrument directly on to a specialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive. Correct disposal avoids negative effects on humans and the environment and ensures recycling of useful raw materials.

KROHNE SU 600 Ex Specifications

General IconGeneral
BrandKROHNE
ModelSU 600 Ex
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals