Maintenance
Actuators IC 40 suffer little wear and require little ser-
vicing. We recommend a function check once a year.
If the “Service note” option has been activated in
BCSoft, a warning signal is issued as standard once
one or several of the set limit values has/have been
reached and exceeded. The warning limits are preset
as follows and can be adapted if necessary:
3 million cycles (0 – 90 – 0°/0 – 100 – 0%),
3 million relay switching operations,
5 million changes of direction.
If a service note is active, it can only be acknowl-
edged via BCSoft. In doing so, the current date will
be entered as the acknowledgement date in the
device history.
Assistance in the event of warnings
and faults
Read the warning, error and fault messages in
the BCSoft diagnostic system.
WARNING
To avoid harm to persons and damage to the unit,
please observe the following:
Electric shocks can be fatal! Before working on
electrically live components, ensure they are
disconnected from the power supply.
Never remove the circuit board!
Unauthorized repairs or incorrect electrical con-
nections may cause the control element to open
resulting in defects.
? Warning and fault
! Cause
Remedy
There are three ways of resetting/
acknowledging warnings and faults:
Reset using BCSoft
Reset by disconnecting the mains voltage and
switching it on again
Reset by pressing the Reset button in the device
(Attention: in the case of electrically live parts, this
may only be carried out by authorized personnel)
RESET
? Red LED lights up and blue LED flashes?
(fault/device error)
! Flashes once: internal fault.
Carry out reset the actuator is recalibrated.
If it is not possible to remedy the fault, send the
actuator to the manufacturer.
! Flashes twice: zero position check, reference
switch does not close.
Carry out reset the actuator is recalibrated.
If it is not possible to remedy the fault, send the
actuator to the manufacturer.
! Flashes 3 times: zero position check, reference
switch does not open.
Carry out reset the actuator is recalibrated.
If it is not possible to remedy the fault, send the
actuator to the manufacturer.