5 UtilityMode
6 BatteryMode
7 BatterySelf-diagnostics
8 Inverterisstartingup
9 ECOMode
10 EPOMode
11 MaintenanceBypassMode
12 FaultMode
3-5 AlarmorFaultreferencecode
Eventlog UPSAlarmWarning Buzzer LED
1 RectifierFault Beepcontinuously FaultLEDlit
2
Inverterfault(IncludingInverter
brid
eisshorted)
Beepcontinuously FaultLEDlit
9 Fanfault Beepcontinuously FaultLEDlit
12 Selftestfault Beepcontinuously FaultLEDlit
13 BatteryChargerfault Beepcontinuously FaultLEDlit
15 DCBusovervoltage Beepcontinuously FaultLEDlit
16 DCBusbelowvoltage Beepcontinuously FaultLEDlit
17 DCbusunbalance Beepcontinuously FaultLEDlit
18 Softstartfailed Beepcontinuously FaultLEDlit
19 UPSInsideOverTemperature Twicepersecond FaultLEDlit
20 HeatsinkOverTemperature Twicepersecond FaultLEDlit
26 Batteryovervoltage Oncepersecond FaultLEDblinking
29 OutputShort-circuit Oncepersecond FaultLEDblinking
30 Inputcurrentlimit Oncepersecond FaultLEDblinking
31 Bypassovercurrent Oncepersecond BPSLEDblinking
32 Overload Oncepersecond
INVorBPSLED
blinkin
33 Nobattery Oncepersecond BatteryLEDblinking
34 Batteryundervoltage Oncepersecond BatteryLEDblinking
35 Batterylowpre-warning Oncepersecond BatteryLEDblinking
36 Overloadtimeout Onceper2seconds FaultLEDblinking
37 DCcomponentoverlimit. Onceper2seconds INVLEDblinking
39 Mainsvolt.Abnormal
Onceper2seconds
BatteryLEDlit
40 Mainsfreq.abnormal
Onceper2seconds
BatteryLEDlit
41 BypassNotAvailable BPSLEDblinking