EasyManuals Logo

KYORITSU 4118A User Manual

KYORITSU 4118A
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
14
  In the event of a fault, the Fault loop impedance should be low enough
(and the Prospective Fault current higher enough) in order to have the
automatic disconnection of supply by the installed protection device within
prescribed time interval.
  Every circuit must be tested to make sure that the fault loop impedance
does not exceed that specified for the over current protection device
concerned.
  For TT system the Fault loop impedance is the sum of the following partial
impedances:
  Impedance of power transformer's secondary.
  Phase conductor resistance from power transformer to fault location.
  Protection conductor resistance from fault location to local earth
system.
  Resistance of local earth system R.
  Resistance of power transformer's earth system Ro.
The figure below shows in marked line the Fault loop impedance for TT
system.
Fig.6
For TN system the Fault loop impedance is the sum of the following
partial impedances:
  Impedance of power transformer's secondary
  Phase conductor resistance from power transformer to fault location
 
Protection conductor resistance from fault location to power transformer

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KYORITSU 4118A and is the answer not in the manual?

KYORITSU 4118A Specifications

General IconGeneral
BrandKYORITSU
Model4118A
CategoryTest Equipment
LanguageEnglish

Related product manuals