EasyManua.ls Logo

KYORITSU 6010A - Testing RCDs used to provide supplementary protection. (FAST TRIP TEST); Testing time delayed RCDs

KYORITSU 6010A
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
10
Set the function switch to X1 for thetriptest, which measures the time
taken for the RCD to trip with the set residual current.
11Set the "LOOP/RCD" switch to 0°
12 Make sure that the P-E and P-N wiring check lamps are lit. If they are not,
disconnect the tester and check the wiring for a possible fault.
13 If the lamps are lit, press the test button to apply full rated tripping current
and the RCD should trip, the tripping time being shown on the display. If
the RCD has tripped the PN and PE LEDs should be off. Check this is so.
14 Repeat the test with the "LOOP/RCD" switch at 180
°
15 MAKE SURE TO KEEP CLEAR OF EARTHED METAL DURING THE
OPERATION OF THESE TESTS.
7.4
 
Testing RCDs used to provide supplementary protection. (FAST TRIP
TEST)
RCDs rated at 30 mA or less are sometimes used to provide extra protection
against electric shock. Such RCDs require a special test procedure as follows:-
1Set the "RCD"switch to "150 FAST".
2Set the "LOOP/RCD" switch to 0°
3Connect the test instrument to the RCD to be tested.
4 Make sure that the P-E and P-N wiring check lamps are lit. If they are not,
disconnect the tester and check the wiring for a possible fault.
5 If the lamps are lit, press the test button to apply a test current of 150mA
where the RCD should trip within 40ms, the tripping time being shown on
the display.
6 Repeat the test with the "LOOP/RCD" switch at 180°
7MAKE SURE TO KEEP CLEAR OF EARTHED METAL DURING THE
OPERATION OF THIS TEST.
7.5
 
Testing time delayed RCDs
RCDs with a built-in time delay are used to ensure discrimination, that is, that
the correct RCD operates first. Testing is carried out in accordance with item
7.3 above, except that the displayed tripping times are likely to be longer than
those for a normal RCD. Since the maximum test time is longer, there may be
danger if earthed metal is touched during the test.
MAKE SURE TO KEEP CLEAR OF EARTHED METAL DURING THE
OPERATION OF THIS TEST.
Note If the RCD does not trip the tester will supply the test current for a
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

Related product manuals