264
9 Faults
No. Description D1 D2 Extra
288 Required dynamics for at least one actuator is miss-
ing
The actual position of the actuator has not changed
for more than 24 h.
– Check air damper and gas damper for
jamming
– Replace the affected actuator
0 = Actuator’s
dynamics
1 = Correction
channel’s
dynamics
Channel number
for actuator or
correction
(starting at 0)
WA = 9
Reset
289 Invalid curve ID of the actual curve set
Reason:
– Wrong curve set loaded
– EEPROM defect
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to
the technical support.
– Replace the device
Curve set 0 R = 0
Power ON
Reset
290 Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
291 Invalid configuration
Incorrect parameter setting Code position Value R = 0, 0, 0, 0
Reset
300 - 313 Internal fault 0 0
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
314 Duration of ambient light monitoring was not met [s]
Duration (5 s) of the ambient light monitoring was not
met. The fault may occur during an internal self-test
.– Reset fault and switch mains OFF and ON if
necessary
– If the fault still exists replace the device.
measured time in
steps of 20 ms
0 R = 0
Power ON Reset
315 - 347 Internal fault 0 0
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
348 Ignition air is missing
Internal
information
0 R = 0
Power ON Reset
349 - 354 Internal fault 0 0
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device