10’ PDUs
19’ PDUs
Zero-U PDUs
Data sheet: S000093176EN-05 Updated: 29/03/2018 Created: 25/10/2016
Cat. Nos: 6 468 00/01/05/06/07/09/10/11/12/13/14/15/18/19/
20/21/22/23/24/30/31/32/33/35/36/40/41/42/43/44/
45/50/51/52/53/54/56/57/59/60/61/65/70/75/90/92/94/
95/97/98/99
51.
1
52
View from above
End viewSide viewEnd view
1U casing
Ze
ro-U casing
- Outlet modules:
PC/ABS
CW507L (CuZn 36) brass
- Fixing brackets:
DC01-A-m galvanised steel
1.3 Standards, regulations and tests
Depending on what equipment they comprise, the PDUs comply with
the current applicable standards below:
Application Standard
French/Belgian standard plugs/outlets
IEC/TR 60083
German standard plugs/outlets
UK standard plugs/outlets + electrical accessories
Italian standard outlets
Swiss standard outlets
C13 and C19 connectors for electrical equipment IEC 60320-2-2
Low voltage surge protection device IEC 6164-11
Switch IEC 60058-1
MCB IEC 60898-1
RCBO IEC 61008-1
Thermal circuit breaker IEC 60730-2-9
Industrial plug IEC 60309-1
Information-processing equipment IEC 60950-1
IP: IP40 for French/Belgian, German, Swiss, Italian and UK standards and
IP20 for electrical appliance connectors (C13 and C19)
IK07
Glow-wire flammability test: The various different standard outlets and
the other functions that equip the PDUs meet the requirements of their
respective standards relating to abnormal heat and fire resistance and
comply with the following thresholds:
- Plastic parts in contact with live parts: 750 °C
- Other plastic parts: 650 °C
Temperature rise: The PDUs are compliant with the standard
temperature rise limit of 45 °C for French/Belgian, German, Swiss and
Italian standards and electrical appliance connectors (C13 and C19) and
52 °C for the UK standard.
Final inspection: Compliant with European standard requirements and
Legrand's own manufacturing requirements, all products undergo
production tests, including:
- Electrical continuity to ensure the product is wired correctly
- Dielectric strength at 2000 V to ensure there is no leakage current
- Operating test
RoHS and REACH conformity: The PDUs comply with European
standards and therefore meet the requirements of the RoHS directive
(Restriction of Hazardous Substances) and REACH regulations
(Registration, Evaluation, Authorisation & restriction of CHemicals).