4.3.5 Battery quantity setting
4.3.6 Bypass Volt-Hi setting
When under the battery capacity setting press On▼ or
when under bypass voltage upper limit setting press
Off▲, it goes to the battery quantity setting. The battery
quantity line flashes as in above picture.
• Use button Enter to choose the different battery
quantity. Battery quantity range is 16, 18, 20.
• Press▲ or ▼ to exit the battery quantity setting
(save the battery quantity setting) and goes to bat-
tery capacity setting or bypass voltage upper limit
setting.
When under the battery quantity setting press On▼ or
when under bypass voltage lower setting press Off▲, it
goes to the bypass upper limit setting. The bypass upper
limit line flashes as in above picture.
• Use button Enter to set the different bypass
voltage upper limit. The bypass voltage upper
limit range is 5%,10%,15%,25% (25% only for 220V
output).
• Press▲ or ▼ to exit the bypass voltage upper limit
setting (save the bypass voltage upper limit setting)
and goes to battery quantity setting or bypass volta-
ge lower limit setting.
Battery quantity setting
(Note: Inside the broken line is
the flashing part.)
Bypass voltage upper limit
setting
(Note: Inside the broken line is
the flashing part.)