PREMIUS
1-10 kVA
Inspect the UPS carefully for shipping damage before installation. Retain the packing material for future use.
3.1 Unpacking
3.1.1 Standard package contents:
User manual
USB cable
Connecting cable for battery
IEC output cables (for 1-3 kVA UPS only)
Input cable – Power cord (for 1 kVA only)
Input cable – Hard wire (for 2-3 kVA)
Model
Wire Size in
sq. mm./No. of Runs
Recommended
Input Breaker
Recommended
Battery Breaker
1 kVA – FM /FMI 2.5/3 16A AC (C Curve) 50A DC (C Curve)
2 kVA – FM /FMI 6/3 32A AC (C Curve) 50A DC (C Curve)
3 kVA – FM /FMI 10/3 40A AC (C Curve) 63A DC (C Curve)
5-6 kVA – FM /FMI 16/3 63A AC (C Curve) 50A DC (C Curve)
7.5-10 kVA – FM /FMI 25/3 100A AC (C Curve) 63A DC (C Curve)
3.2 Selecting Installation Position
Install the UPS in a proper environment to minimize the possibility of damage to the UPS and to extend the
life of the UPS. Please follow these rules:
1. Keep at least 30 cms (12 inches) clearance from the rear panel
of the UPS to the wall
2. Do not block the air flow to the ventilation openings of the unit
3. Ensure that the installation site is not excessively hot or moist
4. Do not place the UPS in an environment near dust, corrosive or
salty material, or flammable objects
5. Do not expose the UPS to the outdoors
3 Installation and Operation
INPUTLOAD
Foult
Low
Testing
UPS
KVA
WHz
Mine
%
0
C
88.8
Parallal ID Mode
Bypass Stop
Utility Invertar
Voltage Adjust
Frequency Window
Buzzer Code
Battery Autonomy
Overload Service
Bypass
Utility
?
Wiring Fault
Alarm
!
Relative humidity
(non condensation

Related product manuals