What to do if the LEGRAND PREMIUS shows a red fault LED?
- CChristian MossOct 31, 2025
If the LEGRAND UPS displays a red fault LED, take the following steps: 1. Ensure proper battery connection, then recharge the batteries for 8 hours to see if the UPS provides backup power normally. 2. If the breaker is tripped, turn off the UPS completely and keep the CAM switch at the INV position before pressing the breaker. Also, reduce the load on the UPS output. 3. Remove any short circuits at the EPO terminal. 4. Clear any obstructions from the ventilation holes. 5. Confirm that the cooling fans on the rear panel are functioning correctly. 6. Ensure the UPS is operating normally. If in CVCF mode, turn the UPS off and then on again. 7. Verify that all parameters except the ID Number are the same for a parallel UPS. 8. Disconnect and reconnect the RJ45 connector or set a UPS w...