Rating Capacity (kVA/kW) 5 kVA/5 kW 6 kVA/6 kW 7.5 kVA/7.5 kW 10 kVA/10 kW
BATTERY
Battery Type Depending on the capacity of external batteries
Number of Batteries 20
Maximum Battery AH 160
CHARGER
Charging Current 1A/2A/3A/4A (selectable)
Floating Voltage (±1%) 274
INDICATION
Status On LED + LCD
Line Mode, Battery Mode, ECO Mode, Bypass Supply, Battery Low Battery Bad/
Disconnect, Overload, Transferring with interruption,
UPS Fault
Readings on LCD
Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load
Percentage, Battery Voltage, Inner Temperature.
Self-Diagnostics
Front Panel Setting & Software Control, Upon Power-on,
24-hour routine checking
ALARMS
Audible and Visual Line Failure, Battery Low, Transfer to Bypass, System Fault Conditions
PHYSICAL
Dimensions (W x D x H) mm 260 x 692 x 437
Net Weight (kg) 28.5 33
ENVIRONMENTAL
Operating Temperature Operating: 0ºC ~ 40ºC, Storage: -10ºC ~ 50ºC
Noise Level ≤50 dB @ 1M
Relative Humidity 30-90% (without condensation)
INTERFACE
Standard EPO/ROO,RS-232,USB
Option Dry Contact Relay, SNMP/WEB Card, RS 485 card
Compatible Platforms Microsoft Windows series, Linux
Safety Standard EN 62040-1, IS16242:2014
EMC Standard IEC/EN 62040-2