45
MODEL ITEM 1 kVA FM
2 kVA 72 V
FM
2 kVA 96 V
FM
3 kVA 72 V
FM
3 kVA 96 V
FM
OUTPUT
Overload Capacity
(tolerance±1%)
<105% continuous
106-120% UPS shuts down after 30sec at battery mode or transfer
to bypass when the utility is normal.
121-150% UPS shuts down after 10sec at battery mode or transfer
to bypass when the utility is normal.
>150% Immediately trip at battery mode or transfer to bypass when the
utility is normal.
Transfer Time
(AC to DC)
0 ms
Transfer Time (
Inverter to Bypass)
4 ms (Typical)
BATTERY
Battery Type Depending on the capacity of external batteries
Number of Batteries 3 6 8 6 8
Maximum Battery AH 160
Rated Battery Voltage 36 V 72 V 96 V 72 V 96 V
CHARGER
Charging Current 2A/4A/6A/8A (selectable)
Floating Mode
Charging Voltage(±1%)
40.9 V±1% 81.9 V±1% 109.2 V±1% 81.9 V±1% 109.2 V±1%
Indication
LED
Utility Normal, Battery Mode, Programmable Outlet1/ Programmable
Outlet2, Bypass Mode & Fault
LCD
Voltage –Input, Output, Battery. Frequency – Input, Output.
Current –Output & Load level % Warning & Fault codes.
Audible
Alarm
Battery Mode Sounds once every 1.5 seconds
Low Battery Sounds once every 0.2 seconds
Overload Continuous tone
Normal Alarm Sounds once every 3 seconds
Fault Continuous tone
Protection
Short Circuit
Normal Mode: Output Breaker/Electronic Circuit Battery Mode: Output
Breaker/Electronic Circuit
Battery Battery Low & High / Electronic Circuit
EPO UPS shuts down immediately
Over Temperature
Normal Mode: Transfer to Bypass Mode
Battery Mode: UPS shuts down immediately