507270-03 Page 5 of 60Issue 1917
Use only the type of gas approved for use with this furnace. 
Refer to unit nameplate.
A95UH1D / A93UH1D  /  95G1UHD  / 92G1UHD units are 
CSA  International  certied  to ANSI  Z21.47  and  CSA  2.3 
standards.
Building Codes
In the USA, installation of gas furnaces must conform with 
local building codes. In the absence of local codes, units 
must  be  installed  according  to  the  current  National  Fuel 
Gas Code (ANSI Z223.1/NFPA 54). The National Fuel Gas 
Code  is  available  from  the American  National  Standards 
Institute, Inc., 11 West 42nd Street, New York, NY 10036.
In Canada, installation must conform with current National 
Standard of Canada CSA-B149 Natural Gas and Propane 
Installation  Codes,  local  plumbing  or  waste  water  codes 
and other applicable local codes.
In order to ensure proper unit operation in non-direct vent 
applications,  combustion  and  ventilation  air  supply  must 
be  provided  according  to  the  current  National  Fuel  Gas 
Code or CSA-B149 standard.
Installation Locations
This  furnace  is  CSA International  certied  for  installation 
clearances  to  combustible  material  as  listed  on  the  unit 
nameplate  and  in  the  table  in  Figure  13  and  Figure  18. 
Accessibility and service clearances must take precedence 
over re protection clearances.
NOTE: For installation on combustible oors, the furnace 
shall  not  be  installed  directly  on  carpeting,  tile,  or  other 
combustible material other than wood ooring.
For installation in a residential garage, the furnace must be 
installed so that the burner(s) and the ignition source are 
located no less than 18 inches (457 mm) above the oor. 
The furnace must be located or protected to avoid physical 
damage by vehicles. When a furnace is installed in a public 
garage,  hangar,  or  other  building  that  has  a  hazardous 
atmosphere,  the  furnace  must  be  installed  according  to 
recommended  good  practice  requirements  and  current 
National Fuel Gas Code or CSA B149 standards.
NOTE: Furnace must be adjusted to obtain a temperature 
rise  within  the  range  specied  on  the  unit  nameplate. 
Failure  to  do  so  may  cause  erratic  limit  operation  and 
premature heat exchanger failure.
This  furnace  must  be  installed  so  that  its  electrical 
components are protected from water.
Installed in Combination with a Cooling Coil
When  this  furnace  is  used  with  cooling  units  (Figure  4), 
it  shall  be  installed  in  parallel  with,  or  on  the  upstream 
side of, cooling units to avoid condensation in the heating 
compartment. With a parallel ow arrangement, a damper 
(or other means to control the ow of air) must adequately 
prevent chilled air from entering the furnace. If the damper 
is  manually  operated,  it  must  be  equipped  to  prevent 
operation of either the heating or the cooling unit, unless it 
is in the full HEAT or COOL setting.
When installed, this furnace must be electrically grounded 
according to local codes. In addition, in the United States, 
installation  must  conform  with  the  current  National 
Electric  Code, ANSI/NFPA  No.  70.  The  National  Electric 
Code (ANSI/NFPA No. 70) is available from the following 
address:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit 
must  be  installed  according  to  the  current  regulations  of 
the Canadian Electrical Code Part I (CSA Standard C22.1) 
and/or local codes.
Figure 4. Heating Unit Installed Parallel to Air Handler 
Unit
NOTE: This furnace is designed for a minimum continuous 
return  air  temperature  of  60°F  (16°C)  or  an  intermittent 
operation down to 55°F (13°C) dry bulb for cases where a 
night setback thermostat  is  used. Return air temperature 
must not exceed 85°F (29°C) dry bulb.
This  furnace  may  be  installed  in  alcoves,  closets,  attics, 
basements,  garages,  and  utility  rooms  in  the  upow  or 
horizontal position.
This  furnace  design  has  not  been  CSA  certied  for 
installation  in  mobile  homes,  recreational  vehicles,  or 
outdoors.