Page 16
ELECTRIC HEAT DATA CBA25UHV-048 | CBA25UHV-060 | SINGLE PHASE
Electic Heat
Model Number
Input
Blower
Motor
Full Load
Amps
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
Single Point
Power Source
Volt kW
1
Btuh Ckt 1Ckt 2Ckt 1Ckt 2
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
5 kW ECBA25-5 (16Y36)
Terminal Block
ECBA25-5CB (16Y39)
30A Circuit Breaker
208
3.6 12,300
6.930- - -30- - -- -
- -
220
4.0 13,800
6.932- - -
4
35 - - -- -
- -
230
4.4 15,000
6.933- - -
4
35 - - -- -
- -
240
4.8 16,400
6.934- - -
4
35 - - -- -
- -
7.5 kW ECBA25-7.5 (16Y37)
Terminal Block
ECBA25-7.5CB (16Y41)
45A Circuit Breaker
208
5.6 19,200
6.942- - -45- - -- -
- -
220
6.3 21,500
6.944- - -45- - -- -
- -
230
6.9 23,500
6.946- - -
4
50 - - -- -
- -
240
7.5 25,600
6.948- - -
4
50 - - -- -
- -
10 kW ECBA25-10 (16Y38)
Terminal Block
ECBA25-10CB (16Y42)
60A Circuit Breaker
208
7.2 24,600
6.952- - -
60 - - -- -
- -
220
8.0 27,500
6.954- - -
60 - - -- -
- -
230
8.8 30,000
6.957- - -
60 - - -- -
- -
240
9.6 32,700
6.959- - -
60 - - -- -
- -
12.5 kW ECBA25-12.5CB (16Y43)
(1) 50A and
(1) 25A Circuit Breaker
208 9.4 32,000
6.9461950
4
20 65 70
220 10.5 35,800
6.9482050
4
20 68 70
230 11.5 39,200
6.9502150257
0
240 12.5 42,600
6.95222
4
60 25 74 80
15 kW ECBA25-15CB (16Y44)
(1) 60A and
(1) 25A Circuit Breaker
208
10.8 36,900 6.9522260257
0
220
12.1 41,300 6.9542360257
0
230
13.2 45,100 6.9572460258
0
240 14.4 49,100 6.9592560258
0
20 kW ECBA25-20CB (16Y46)
(1) 60A and
(1) 50A Circuit Breaker
208 14.4 49,200 6.9524360
4
45 95 100
220 16.1 55,000 6.954466050100 100
230 17.6 60,100 6.957486050104 110
240 19.2 65,500 6.959506050109 110
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
1
Electric heater capacity only - does not include additional blower motor heat capacity.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
3
HACR type breaker or fuse.
4
Bold indicates that the circuit breaker on “CB” circuit breaker models must be replaced with size shown. See tablepage 6.