EasyManuals Logo

Lennox CBA25UHV User Manual

Lennox CBA25UHV
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
Page 20
TABLE 11. CBA25UHV Thermostat and Two-Stage Outdoor Unit Operating Sequence
Operating Sequence System Demand System Response
System
Condition
Step
Thermostat Demand Relative Humidity
pressor
Air
Handler
CFM
(COOL) CommentsY1 Y2 O G W1 W2 Status D
NO CALL FOR DEHUMIDIFICATION
Normal Operation
- Y1
1 On On On Acceptable 24 VAC Low 70%
Compressor and indoor air handler follow
thermostat demand
Normal Operation
- Y2
2 On On On On Acceptable 24 VAC High 100%
Room Thermostat Calls for First-Stage Cooling
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable 24 VAC Low 70%
gizes D on a call for dehumidification
Dehumidification
Call
2 On On On On Demand 24 VAC High
60%/65%
70%*
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable 24 VAC Low 70%
midity is greater than set point
Dehumidification
Call
2 On On On On Demand 0 VAC High
60%/65%
70%*
Dehumidification
Call ONLY
1 On On On On Demand 0 VAC High
60%/65%
70%*
midity setpoint by allowing the room
stat setpoint**
Room Thermostat Calls for First- and Second-Stage Cooling
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On On On Acceptable 24 VAC High 100%
gizes D on a call for dehumidification
Dehumidification
Call
2 On On On On Demand 0 VAC High
60%/65%
70%*
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation 1 On On On On Acceptable 24 VAC High 100%
midity is greater than set point
Dehumidification
Call
2 On On On On Demand 0 VAC High
60%/65%
70%*
Dehumidification
Call ONLY
1 On On On On Demand 0 VAC High
60%/65%
70%*
midity setpoint by allowing the room
stat setpoint**
Jumpers at indoor unit with a two-stage outdoor unit
With Condensing unit - Y2 and R to O
With Heat Pump - none
* During dehumidification, cooling air handler speed is as follows: 70% of COOL cfm for 018, 024, 030; 65% for 036; 60% for 042, 048 and 060 units.
** Thermostat will maintain the room temperature up to 2°F (1.2°C) cooler than the room thermostat setting in precision mode.
HEAT JUMPER
The HEAT jumper is used to determine CFM during elec-
tric heat operation only. These jumper selections are acti-
vated only when W1 is energized.
DELAY JUMPER
The DELAY jumper is used to set the specic motor fan
operation during cooling mode. Depending on the appli-
cation, one of four options may be chosen by moving the
jumper to the appropriate set of pins.
#1 Pins Jumpered
A- Motor runs at 100% until demand is satised.
B- Once demand is met, motor ramps down to stop.
OFFOFF
100% CFM
COOLING
DEMAND
#2 Pins Jumpered
A- Motor runs at 100% until demand is satised.
B- Once demand is met, motor runs at 100% for 45 sec-
onds.
C- Motor ramps down to stop.
OF
F
OFF
A
B
C
100% CFM
100% CFM
(60 seconds)
COOLING DEMAND
#3 Pins Jumpered
A- Motor runs at 82% for approximately 7-1/2 minutes. If
demand has not been satised after 7-1/2 minutes.
B- Motor runs at 100% until demand is satised.
C- Once demand is met, motor ramps down to stop.
OFF
OFF
A
B
C
82%CFM
100% CFM
COOLING DEMAND
7 1/2 MIN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CBA25UHV and is the answer not in the manual?

Lennox CBA25UHV Specifications

General IconGeneral
TypeAir Handler
ModelCBA25UHV
BrandLennox
EfficiencyUp to 16 SEER
RefrigerantR-410A
Nominal Voltage208/230V
Width21 inches
CompatibilityCompatible with Lennox outdoor units
Nominal Cooling Capacity1.5 to 5 tons
Motor TypePSC or ECM
Airflow RangeUp to 2000 CFM
MotorVariable Speed Motor

Related product manuals