Page 2
CBX40UHV
MODEL NUMBER IDENTIFICATION
Refrigerant Type
X = R−410A
Series
Nominal Cooling Capacity
024 = 2 tons
030 = 2.5 tons
036 = 3 tons
042 = 3.5 tons
048 = 4 tons
060 = 5 tons
Minor Revision Number
Configuration
UHV = Up−Flow/Horizontal, Variable
Speed Blower Motor
Voltage
230 = 208/230V−60hz−1ph
Refrigerant Metering Device
2 = Fixed Orifice
3 = TXV − Bleedport (indoor unit)
4 = TXV − Non−bleedport (indoor unit)
5 = TXV − Non−bleedport (outdoor unit)
6 = TXV − R−410A Non−bleedport (indoor unit)
Unit Type
CB = Air Handler
CB X 40 UHV − 036 − 230 − 6 − 02
SPECIFICATIONS / ELECTRICAL DATA
Refer to the Unit Engineering Handbook or Lennox Price Book for optional accessories for this unit.
SPECIFICATIONS
GENERAL DATA
MODEL NUMBER
CBX40UHV
-024
CBX40UHV
-030
CBX40UHV
-036
CBX40UHV
-042
CBX40UHV
-048
CBX40UHV
-060
Nominal cooling capacity − tons
2 2.5 3 3.5 4 5
Refrigerant
HFC−410A HFC−410A HFC−410A HFC−410A HFC−410A HFC−410A
Connections
in.
Suction (vapor) line − sweat
3/4 3/4 3/4 7/8 7/8 7/8
Liquid line − sweat
3/8 3/8 3/8 3/8 3/8 3/8
Condensate drain (fpt)
(2) 3/4 (2) 3/4 (2) 3/4 (2) 3/4 (2) 3/4 (2) 3/4
Indoor
Coil
Net face area − ft.
2
5.0 5.0 5.0 7.22 7.22 7.22
Tube outside diameter − in.
3/8 3/8 3/8 3/8 3/8 3/8
Number of rows
3 3 3 3 3 3
Fins per inch
12 12 12 12 12 12
Blower Data
Wheel nominal diameter x width − in.
11 X 8 11 X 8 11 X 8 11−1/2 X 9 11−1/2 X 9 11−1/2 X 9
Motor output − hp
1/2 1/2 3/4 1 1 1
Filters (MERV16)
1
Size − in.
20 X 20 X 5 20 X 20 X 5 20 X 20 X 5 20 X 25 X 5 20 X 25 X 5 20 X 25 X 5
Shipping Data − 1 Package − lbs.
165 167 172 214 216 216
ELECTRICAL DATA
Voltage − phase − 60hz
208/230V−1PH
2
Maximum overcurrent protection (unit only)
15 15 15 20 20 20
Minimum circuit ampacity (unit only)
5 5 10 10 10 10
1
Disposable frame type filter.
2
HACR type circuit breaker or fuse.
REPLACEMENT CIRCUIT BREAKERS
Voltage Description Catalog No.
NOTE − Electric Heat Circuit Breakers are sized for 240VAC operation. Electric
heaters operating at voltages other than 240VAC may require the factory installed
circuit breaker be replaced with a field installed circuit breaker. See Maximum
Overcurrent Protection column in the Electric Heat Tables to determine if a circuit
breaker change is required.
208/240V − 1 Phase 25 amp, 2 pole 41K13
30 amp, 2 pole 17K70
35 amp, 2 pole 72K07
40 amp, 2 pole 49K14
45 amp, 2 pole 17K71
50 amp, 2 pole 41K12
60 amp, 2 pole 17K72
208/240V − 3 Phase 30 amp, 3 pole 18M85
40 amp, 3 pole 41K16
45 amp, 3 pole 18M86
50 amp, 3 pole 41K15
60 amp, 3 pole 41K17