Menu Description 4thdigit 3rddigit 2nddigit 1stdigit R/W/Z Min Std Max
3881
setpointforactivationoperationofcomponent Enabled R/W/Z 0 1 1
3882
setpointofcondensingcontrol SpTemp. R/W 20 30 50
3883
deltatoffullcapacity DeltaT. R/W 1 8 20
3884
Openingthresholdofthefreshairdamperforactivation Opening R/W 0 0 100
3911
setpointofconfiguration Config. R/W 0 0 1
3912
setpointforactivationoperationofcomponent Enabled R/W/Z 0 1 1
3913
integraltimecontrol Ti. R/W 5 30 120
3921
setpointofconfiguration Config. R/W 0 0 2
3922
integraltime
control Ti. R/W 10 60 120
3931
powermeterconfiguration Config. R/W 0 0 1
3932
addressofthepowermeterinthers485bus Address R 21 21 21
3933
speedofthers485bus Baud R 19200 19200 19200
3934
parityofthers485bus Parity R 0 0 0
3935
communicationonrs485iscorrect OnLine R 0 0 1
3936
valueofthecurrent,instantaneous Current R 0 0 999,9
3937
currentthresholdforunloaded50%ofcompressors Max.Cur. R/W 0 0 999,9
3938
valueforresetpowermetermemory Code R/W
32768 0 32767
Expert
Expert
Expert
Other
Other
Other
Expert Economizer Heater
PowerMeter
ChilledWater
Humidifier
CLIMATICRT_UNITARYIOM1508E .94.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CLIMATIC series and is the answer not in the manual?

Lennox CLIMATIC series Specifications

General IconGeneral
ConnectivityWi-Fi
CompatibilityLennox HVAC systems
User InterfaceTouchscreen
Remote AccessYes, via app
Energy ManagementEnergy-saving modes
DisplayColor
Programmability7-day programmable

Related product manuals