Menu Description 4thdigit 3rddigit 2nddigit 1stdigit R/W/Z Min Std Max
3771
settingoffunctionality
Expert Heater Pump
Mode R/W 0 0 3
3781
openingpercentagevalveforfreezeprotection Leak R/W 0 0 50
3782
outsideairtemperaturethresholdtoactivatefunction Onset R/W 20 20 50
3811
configurationoffreshairdamper Damper R/W 0 0 2
3812
configurationofairqualitysensor Co2 R/W 0 0 2
3813
choiceofrecoverymodule Recov. R/W 0 0 4
3814
configurationoffreshairelectricalheaters Heater R/W 0 0 2
3815
choiceofexhaustfan Exhaust R 0 0 2
3816
choiceofkit Kit R/W 0 0 5
3817
choiceofmotorsize Motor R/W 0 0 10
3818
choiceoffantype Fan R/W 0 0 4
3819
choiceofinverterforexhaustfan Inverter R/W 0 0 5
3821
setpointofminimumfreshair Minimum R/W/Z 0 0 100
3822
setpointofmaximumfreshair Maximum R/W 0 100 100
3823
integraltimecontrolfreshairdamper Ti. R/W 5 10 120
3824
stateofenthalpyfunction Enthalpy R/W 5 10 120
3825
stateofcalibrationfunction Calib. R/W 0 0 1
3826
stateofopeningto0%byBMS
Bms0% R/W 0 0 1
3827
stateofopeningto100%byBMS Bms100% R/W 0 0 1
3828
MinimumFreshAir,Choiceofthefunctionality Mode R/W/Z 0 0 1
3829
SetpointofMinimumFreshAir(secondlevel) Mini.2nd R/W/Z 0 0 100
3831
setpointforactivationoperationoffunction Enabled R/W/Z 0 1 1
3832
outsidelowertemperaturethreshold,unload LowL. R/W 20 20 50
3833
outsideuppertemperaturethreshold,unload HighL. R/W 20 26 50
3834
stateof
unloadbyBMS BmsUnl. R/W 0 0 1
3841
setpointforactivationoperationoffunction Enabled R/W/Z 0 1 1
3842
outsidelowertemperaturethreshold,unload LowL. R/W 20 14 50
3843
outsideuppertemperaturethreshold,unload HighL. R/W 20 40 50
3844
stateofunloadbyBMS BmsUnl. R/W 0 0 1
3851
setpointforactivationoperationoffunction Enabled R/W/Z 0 1 1
3852
settingoffunctionality Mode R/W 0 0 1
3853
minimumthresholdforcontrol Minimum R/W 0 1000 2000
3854
maximumthresholdfor
control Maximum R/W 0 1500 2000
3855
upperairqualitythresholdofalarm Limit R/W 0 1500 2000
3856
stateofunloadbyBMS BmsUnl. R/W 0 0 1
3857
valueoftheairqualitysendbyBMS BmsVal. R/W 0 0 2000
3861
openingpercentagethresholdofactuatorfor1stfan Step1 R/W 0 33 100
3862
openingpercentagethresholdofactuatorfor2ndfan Step2 R/W 0 50 100
3863
openingpercentagethresholdofactuatorfor3rdfan
Step3 R/W 0 66 100
3864
nominalthresholdforairflowcontrol FlowH. R/W 0 ~ 100
3865
lowthresholdforairflowcontrol FlowL. R/W 0 ~ 100
3866
coefficientforcompensationoflossesoftheairdamper Coef. R/W 100 0 100
3871
setpointforactivationoperationofcomponent Enabled R/W/Z 0 1 1
3872
setpointofdeltat(outside/return)forstartingwheelmotor Delta.T R/W 1 4 10
3873
outsideairtemperaturethresholdtoactivatedefrost
function Defrost R/W 20 5 20
3874
deltatthreshold(outside/outlet)foralarm Safety R/W 0 2 5
3875
dirtyfiltersthresholdalarm Filters R/W 50 250 500
Economizer Configuration
Expert
Expert
Expert
Expert
Expert
Expert
Economizer
FreeCooling
FreeHeating
Expert Economizer Control
Expert
Economizer
Economizer
Economizer
Economizer
Heater
AirQuality
Exhaust
Recovery
HotWaterReco.
CLIMATICRT_UNITARYIOM1508E .93.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CLIMATIC series and is the answer not in the manual?

Lennox CLIMATIC series Specifications

General IconGeneral
ConnectivityWi-Fi
CompatibilityLennox HVAC systems
User InterfaceTouchscreen
Remote AccessYes, via app
Energy ManagementEnergy-saving modes
DisplayColor
Programmability7-day programmable

Related product manuals