Menu Description 4thdigit 3rddigit 2nddigit 1stdigit R/W/Z Min Std Max
3541
outsideairtemperaturethresholdtoactivatefunction Onset R/W 8 16 22
3542
ratiofordynamicmanagement Ratio R/W 0 1,4 2
3543
minimumtimebetweentwodefrost Timeout R/W 30 45 90
3544
numberrestartoffansfortheendofcycle Restart R/W 1 3 5
3545
choiceofonecompressorbytandemduringdefrost 1/2Tand R/W 0 0 1
3546
stateofdefrostcycledelayedbyBMS BmsWait R/W 0 0 1
3611
setpointofconfiguration
Expert ExpansionValve Configuration
Option R/W 0 0 1
3621
setpointofsuperheat S.Heat R/W 3 5 10
3622
kpsetpointforpidcontrol Kp R/W 0 7 30
3623
tisetpointforpidcontrol Ti R/W 0 60 360
3624
tdsetpointforpidcontrol Td R/W 0 2 9
3625
offsetforpressuresensor Offset R/W 505
3626
offsetfortemperatureprobe Offset R/W 505
3627
choiceofmanualmode Manual R/W 0 0 1
3628
valueofnumberofstepsformanualmode Steps R/W 0 0 480
3631
setpoint
ofsuperheat S.Heat R/W 3 5 10
3632
kpsetpointforpidcontrol Kp R/W 0 7 30
3633
tisetpointforpidcontrol Ti R/W 0 60 360
3634
tdsetpointforpidcontrol Td R/W 0 2 9
3635
offsetforpressuresensor Offset R/W 505
3636
offsetfortemperatureprobe Offset R/W 505
3637
choiceofmanualmode Manual R/W 0 0 1
3638
valueofnumberofstepsformanualmode Steps R/W 0 0 480
3711
1stheaters,setpoint
ofconfiguration Main R/W 0 0 7
3712
2ndheaters,setpointofconfiguration 2nd R/W 0 0 2
3713
Hotwaterpump,setpointofconfiguration Pump R/W 0 0 1
3721
1stheaters,setpointforactivationoperationofcomponent Enable.1 R/W/Z 0 1 1
3722
1stheaters,stateofunload50%byBMS Bms50% R/W 0 0 1
3723
1stheaters,stateofunload100%byBMS BmsUnl. R/W 0 0 1
3724
2ndheaters,setpointforactivationoperationof
component Enable.2 R/W/Z 0 1 1
3731
1stheaters,setpointforpriorityinversionstarting Swap1 R/W/Z 0 0 3
3732
1stheaters,outsideairtemperaturethresholdforswapcontrol Swap1 R/W 20 10 50
3733
1stheaters,outsideairtemperaturethresholdforunload LowL.1 R/W 20 10 50
3734
1stheaters,deltatofonestage DeltaT.1 R/W 1 8 20
3735
1stheaters,integraltimecontrol Ti.1 R/W 5 30 120
3736
2ndheaters,
setpointforpriorityinversionstarting Swap2 R/W/Z 0 0 1
3737
2ndheaters,deltatofonecompressor DeltaT.2 R/W 1 8 20
3738
2ndheaters,integraltimecontrol Ti.2 R/W 5 30 120
3751
setpointoflimitmaximumpower
Expert Heater Electrical
TriacMax R/W 0 100 100
3761
openingpercentagevalveforfreezeprotection Leak R/W 0 0 50
3762
outsideairtemperaturethresholdtoactivatefunction Onset R/W 20 20 50
3763
choicetocloseoropenvalve
incaseoffreezingalarm Freeze R/W 0 0 1
Expert
Expert
Expert
Expert
Expert
Expert
Expert
Heater
Heater
Heater
Condenser
ExpansionValve
ExpansionValve
Heater
HotWater
Defrost
Circuit1
Circuit2
Configuration
Mode
Control
CLIMATICRT_UNITARYIOM1508E .92.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CLIMATIC series and is the answer not in the manual?

Lennox CLIMATIC series Specifications

General IconGeneral
ConnectivityWi-Fi
CompatibilityLennox HVAC systems
User InterfaceTouchscreen
Remote AccessYes, via app
Energy ManagementEnergy-saving modes
DisplayColor
Programmability7-day programmable

Related product manuals