Menu Description 4thdigit 3rddigit 2nddigit 1stdigit R/W/Z Min Std Max
3331
settingoffunctionality Function R/W/Z 0 0 2
3332
choiceofmode(%orqv) Mode R/W 0 0 1
3333
nominalthresholdforairflowcontrol FlowH. R/W/Z 0 ~ 100
3334
lowthresholdforairflowcontrol FlowL. R/W/Z 0 ~ 100
3335
coefficientforcompensationoflossesoftheairdamper Coef. R/W 100 0 100
3336
minimumthresholdforairflowcontrol Minimum R/W 0 ~ 100
3337
maximumthresholdforairflowcontrol Maximum R/W 0 ~ 100
3341
choiceof
airflowsensor Config. R 0 0 2
3342
valueoftheairflowsensor Delta.P R 0 0 1000
3343
airflowthresholdalarm AirFlow R/W 0 25 1000
3344
filtersmissingthresholdalarm Missing R/W 0 50 1000
3345
dirtyfiltersthresholdalarm Dirty R/W 50 250 1000
3351
lowspeedforcedbyBMS BmsLow R/W 0 0 1
3352
highspeedforcedbyBMS BmsHigh R/W 0 0 1
3353
valueofthespeedsendbyBMS BmsVal. R/W 0 0 100
3411
choiceofmodulatedcompressor Modul. R/W 0 0 2
3412
configurationofleakdetectionmanagement LeakDet. R/W 0 0 1
3413
configurationofsensorsinstalledonthecircuits Sensor R/W 0 4 4
3421
setpointforactivationoperationofallcompressor,cooling/heatingmode Enabled R/W/Z 0 1 1
3422
enablecircuit1,separatecomp.1or/andcomp.2 Enable.1 R/W 0 0 3
3423
enablecircuit2,separatecomp.1or/andcomp.2 Enable.2 R/W 0 0 3
3424
stateofunload50%byBMS Bms50% R/W 0 0 1
3425
stateofunload100%
byBMS BmsUnl. R/W 0 0 1
3426
stateofunloadheatpumpbyBMS BmsHPum R/W 0 0 1
3431
setpointforactivationoperationincoolingmode Enabled R/W/Z 0 1 1
3432
outsideairtemperaturethreshold,unload50%ofcompressors LowL50% R/W 10 20 50
3433
outsideairtemperaturethreshold,unload100%ofcompressors LowL. R/W 10 12 50
3434
deltatofonecompressor DeltaT. R/W 1 8 20
3435
integraltimecontrol,compressorin
coolingmode Ti. R/W 5 30 120
3441
setpointforactivationoperationinheatingmode Enabled R/W/Z 0 1 1
3442
outsideairtemperaturethreshold,unload50%ofcompressors LowL50% R/W 20 20 50
3443
outsideairtemperaturethreshold,unload100%ofcompressors LowL. R/W 20 20 50
3444
deltatofonecompressor DeltaT. R/W 1 8 20
3445
integraltimecontrol,compressorinheatingmode Ti. R/W 5 30 120
3511
setpointof
configuration Type R/W 0 0 1
3512
choiceofmodulationmode Modul. R/W 0 0 4
3521
choiceofcontrolmode Mode R/W/Z 0 0 3
3522
setpointofthecondensingtemperature Cond. R/W 25 30 45
3523
speedpercentageforreducedmode Reduced R/W 70 70 100
3524
tisetpointforpidcontrol Ti. R/W 70 70 100
3531
lowerwatertemperaturethreshold LowL. R/W 4 5 20
3532
upperwatertemperaturethreshold HighL. R/W 20 45 50
3533
openingpercentagevalveforfreezeprotection Leak R/W 0 0 50
3534
outsideairtemperaturethreshold
toactivatefunction Onset R/W 20 20 50
Expert
Expert
Expert
Expert
Expert
Expert
Expert
Expert
Expert
Expert
Condenser
Blower
Compressor
Compressor
Compressor
Compressor
Condenser
Condenser
Blower
Blower
Mode
Cooling
Heating
Configuration
Savety
Speed
Safety
Bms
Configuration
Control
CLIMATICRT_UNITARYIOM1508E .91.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CLIMATIC series and is the answer not in the manual?

Lennox CLIMATIC series Specifications

General IconGeneral
ConnectivityWi-Fi
CompatibilityLennox HVAC systems
User InterfaceTouchscreen
Remote AccessYes, via app
Energy ManagementEnergy-saving modes
DisplayColor
Programmability7-day programmable

Related product manuals