Menu Description 4thdigit 3rddigit 2nddigit 1stdigit R/W/Z Min Std Max
3221
offsetforroomtemperaturevalue Offset R/W 505
3222
roomtemperaturethresholdforunloadingcoolingmode LimitC. R/W 0 0 40
3223
roomtemperaturethresholdforunloadingheatingmode LimitH. R/W 0 40 40
3224
externalvalueofsetpointforcontroltemperature 420m
A
R 505
3225
Dynamicsetpoint(coolingsetpointoffsetaccordingtooutsidetemperature) Sp.Dyna. R/W/Z 0 20 20
3226
setpointofcoolingmode Sp.Cool. R/W/Z 8 22 35
3227
setpointofheatingmode Sp.Heat. R/W/Z 8 19 35
3228
integraltimecontrolforcoolingmode Ti.Cool. R/W 10 60 120
3229
integraltimecontrolforheatingmode Ti.Heat. R/W 10 60 120
3231
activationofthesmoothingfunctionoftemperature Smooth R/W/Z 0 0 1
3232
lowlimitthresholdincoolingmode Lim.Cool R/W 4 4 58
3233
highlimitthresholdinheatingmode Lim.Heat R/W 4 38 58
3234
offsetforhighlimitthresholdincoolingmode Adj.Cool R/W 505
3235
offsetforlowlimitthresholdinheatingmode Adj.Heat R/W 505
3236
outdoortemperaturelowthresholdforslopeonthesupplytemperaturesetpoint Out.Low R/W 20 0 50
3237
coefficientofthelowoutsidetemperaturefortheslopeofthesupplytemperature
setpoint Coef.Low R/W 50 0 50
3238
outdoortemperaturehighthresholdforslopeonthesupplytemperaturesetpoint Out.High R/W 20 30 50
3239
coefficientofthehighoutsidetemperaturefortheslopeofthesupplytemperaturesetpoint Coef.High R/W 50 0 50
3241
setpointforactivationoperationofcontrol Enable R/W/Z 0 0 1
3242
setpointofdehumidification Sp.Deh. R/W/Z 0 100 100
3243
setpointofhumidification Sp.Hum. R/W/Z 0 0 100
3244
integraltime
controlfordehumidification Ti.Deh. R/W 10 60 120
3245
integraltimecontrolforhumidification Ti.Hum. R/W 10 60 120
3251
lowersupplytemperaturethreshold,1stlevelofalarm SupLo.1 R/W 5 6 19
3252
lowersupplytemperaturethreshold,2ndlevelofalarm SupLo.2 R/W 1 2 17
3253
uppersupplytemperaturethreshold,1stlevelofalarm SupHi.1 R/W 20 40 70
3254
uppersupplytemperaturethreshold,2ndlevelofalarm SupHi.2 R/W 20 60 70
3255
lowerroom
temperaturethresholdofalarm RoomLo. R/W 5 5 40
3256
upperroomtemperaturethresholdofalarm RoomHi. R/W 5 40 40
3257
dewpointcontrol DewPoint R/W 0 0 1
3258
lowerroomhumiditythresholdofalarm RoomLo. R/W 0 0 100
3259
upperroomhumiditythresholdofalarm RoomHi. R/W 0 100 100
3261
stateofunloadcoolingmodebyBMS Cool.Mod R/W 0 0 1
3262
stateofunloadcoolingmodebyBMS Heat.Mod R/W 0 0 1
3263
valueoftheoutside
temperaturesendbyBMS Out.T. R/W 99,9 99,9 99,9
3264
valueoftheroomtemperaturesendbyBMS RoomT. R/W 99,9 99,9 99,9
3265
valueoftheoutsidehumiditysendbyBMS Out.Hr. R/W 0 0 100
3266
valueoftheroomhumiditysendbyBMS RoomHr. R/W 0 0 100
3311
choiceofairflowsensor AirFlow R/W 0 0 1
3312
choiceofinverter Modul. R/W 0 0 2
3313
choiceofkit Kit R/W 0 0 5
3314
choiceofmotorsize Motor R/W 0 0 10
3315
choiceoffantype Fan R/W 0 0 4
3321
setpointforactivationoperationofcomponent Enable R/W/Z 0 1 1
3322
setpointforactivationoperationinroomcontroldeadzone DeadZ. R/W/Z 0 0 2
3323
temperaturethresholdforactivationnightrefreshmentfunction NightEco R/W 8 22 35
3324
time,cyclicdeadzonefunction,fanon TimeOn R/W 0 300 32400
3325
time,cyclicdeadzonefunction,fanoff Time
Of
f
R/W 0 3300 32400
Expert
Expert
Expert
Expert
Expert
Expert
Expert
Control
Control
Blower
Control
Control
Control
Blower
Configuration
Mode
Room
Supply
Humidity
Safety
Bms
CLIMATICRT_UNITARYIOM1508E .90.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CLIMATIC series and is the answer not in the manual?

Lennox CLIMATIC series Specifications

General IconGeneral
ConnectivityWi-Fi
CompatibilityLennox HVAC systems
User InterfaceTouchscreen
Remote AccessYes, via app
Energy ManagementEnergy-saving modes
DisplayColor
Programmability7-day programmable