Page 16
Instal-
lerSet−
Up No.
Notes
Selection Description
(Factory setting in bold print)
Installer
Set−Up
Name
0360
Heat
Pump
Auxiliary
Heat
Lock−Out
0 − No auxiliary heat lock−out. Factory
setting.
40°F (4.5°C).
45°F (7°C)
50°F (10°C).
55°F (13°C).
60°F (15.5°C).
Shown only if
electric is se-
lected for back−
up heat source
and outdoor
temp. sensor
for control is se-
lected.
0500
Filter
Change
Remind-
er
0 − Filter change reminder off. Factory
setting.
1 − 10 run time days.
2 − 30 run time days.
3 − 60 run time days.
4 − 90 run time days.
5 − 120 run time days.
6 − 365 run time days.
Run time based
on call for fan.
0510
Humidifi-
er Pad
Replace-
ment
Remind-
er
0 − Humidifier pad replacement remind-
er off. Factory setting.
1 − 90 run time days.
2 − 180 run time days.
3 − 365 run time days.
0520
UV Lamp
Replace-
ment Re-
minder
0 − UV lamp replacement reminder off.
Factory setting.
1 − 365 run time days.
0530
Adaptive
Intelligent
Recovery
0 − Conventional Recovery −− System
starts recovery at programmed time.
1 − Adaptive Intelligent Recovery −− Sys-
tem starts recovery early so that set-
point is reached by the start of the pro-
gram period. Factory setting.
0540
Number
of Peri-
ods
2 − Two periods (wake and sleep) avail-
able.
4 − Four periods (wake, leave, return,
sleep) available. Factory setting.
Shown only
when program-
mable is cho-
sen.
Setting applies
to all days of
the week.
0580
Minimum
Com-
pressor−
Off Time
Settings of 0 − 5 available.
5 − Five−minute compressor−off time
setting. Factory setting.
table continued on next page