26
Normal
In this mode, dehumidication occurs if these con-
ditions are met and signals are present at specic
terminals:
1. Dehumidication has been enabled on
installer settings, and
2. Unit is in COOL mode
3. Dehumidication demand exists (RH above
set point)
4. Cooling demand exists (Y1 energized).
Max
In this mode, dehumidication occurs if all maximum
conditions are true, except cooling demand may or
may not be present. Maximum over cool from cool-
ing set point is 2ºF.
RTU/Aux Dehumidier
When dehumidify mode is in “RTU/AUX dehumidi-
er”, “D” terminal works in active logic.
The RTU/Aux dehumidier setting is used with RTU
with rooftop units only when a dehumidier is used
for dehumidication. This requires:
1. Dehumidier has been wired to thermostat per
dehumidier installation instructions.
2. Dehumidication has been enabled on installer
settings.
3. Unit is in COOL mode, (or if in AUTO, there has
been at least one thermostat cooling call made
prior to the dehumidication demand).
4. Dehumidication demand exists (RH above set
point).
Humiditrol®
This setting is for commercial split systems only. If
Humiditrol is enabled in the installer settings, then
this adjustment aects over-cooling operation.
Over-cooling ranges from 2ºF below the cooling
setpoint (MIN setting) down to 2ºF above the
heating setpoint (MAX setting). Halfway between
the two settings is the MID setting.
If a Humiditrol® EDA is installed and enabled,
then the thermostat must be congured to properly
operate the Humiditrol® EDA as follows (see Figure
15 for the Humiditrol® EDA operation owchart):
Check the HUMIDITY SETTINGS in user
settings to conrm that the user has turned ON
dehumidication setting.
NOTE: Humiditrol
®
EDA operation requires use
of an outdoor sensor. If sensor is not
connected and Humiditrol
®
EDA is enabled,
“OUTDOOR SENSOR REQUIRED” is
displayed in the information display.
Cooling only - Dehumidication will only occur if:
1. Dehumidication demand is present
2. Cooling demand is not present
3. Outdoor temperature is less than 95ºF
4. Indoor temperature is not cooler than 65ºF or
cooler than the heating set point + 2ºF (IF the
dierence between cooling and heating set
points is greater than the deadband).