EasyManua.ls Logo

Lennox EL16XC1 Series

Lennox EL16XC1 Series
31 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 3
EL16XC1 SERIES
Electrical Data
208/230V - 60 Hz - 1 ph
Model Numbers
Unit Compressor Condenser Fan
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
2
Rated Load
Amps (RLA)
Locked Ro
tor Amps
(LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
Locked Ro
tor Amps
(LRA)
EL16XC1-018 20 11.9 9.0 48.0 1/10 1075 0.7 1.3
EL16XC1-024 25 14.6 10.9 59.3 1/6 825 1.0 1.9
EL16XC1-030 25 17.0 12.8 67.8 1/6 825 1.0 1.9
EL16XC1-036
EL16XC1S036
30 18.0 13.6 79.0 1/6 825 1.0 1.9
EL16XC1-041 30 19.3 14.7 75.0 1/6 825 1.0 1.9
EL16XC1-042 40 23.4 17.9 112.0 1/6 825 1.0 1.9
EL16XC1-047 35 21.9 16.1 105.5 1/3 825 1.8 2.9
EL16XC1-048 40 24.2 18.0 117.0 1/4 825 1.7 3.2
EL16XC1-060 50 29.6 22.2 127.9 1/3 825 1.8 2.9
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

Related product manuals