Page 23
INTERIOR MAKE-UP BOX INSTALLATION
BOX
Right Side
Figure 28 
 WARNING
Fire Hazard. Use of aluminum wire with this product 
may result in a re, causing property damage, severe 
injury or death. Use copper wire only with this product.
Refer to gure 29 for schematic wiring diagram, eld wir-
ing and trouble shooting.
The power supply wiring must meet Class I restrictions. 
Protected by either a fuse or circuit breaker, select circuit 
protection and wire size according to unit nameplate.
 CAUTION
Failure to use properly sized wiring and circuit breaker 
may result in property damage. Size wiring and circuit 
breaker(s) per Product Specications bulletin (EHB) 
and unit rating plate.
NOTE -  Unit  nameplate  states  maximum  current  draw. 
Maximum over-current protection allowed is 15 AMP
 Holes are on both sides of the furnace cabinet to facilitate 
wiring.
Install a separate (properly sized) disconnect switch near 
the furnace so that power can be turned off for servicing. 
Before connecting the thermostat, check to make sure 
the wires will be long enough for servicing at a later date. 
Make sure that thermostat wire is long enough to facilitate 
future removal of blower for service.
Complete the wiring connections to the equipment. Use 
the provided unit wiring and eld wiring diagram shown in 
gure 29. Use 18-gauge wire or larger that is suitable for 
Class II rating for thermostat connections.
Electrically ground the unit according to local codes or, in 
the absence of local codes, according to the current Na-
tional Electric Code (ANSI/NFPA No. 70). A green ground 
wire is provided in the eld make-up box.
NOTE - The EL180UHE furnace contains electronic com-
ponents that are polarity sensitive. Make sure that the fur-
nace is wired correctly and is properly grounded.
 WARNING
Electric Shock Hazard. Can cause injury or 
death. Unit must be properly grounded in 
accordance with national and local codes.
Accessory Terminals
One line voltage “EAC” 1/4” spade terminal is provided on 
the furnace integrated control. See gure 30 for integrated 
control conguration. This terminal is energized when the 
indoor blower is operating. Any accessory rated up to one 
amp can be connected to this terminal with the neutral leg 
of the circuit being connected to one of the provided neu-
tral  terminals.  If  an  accessory  rated  at  greater  than  one 
amp is connected to this terminal, it is necessary to use 
an external relay.
One line voltage “HUM” 1/4” spade terminal is provided on 
the furnace integrated control. See gure 30 for integrat-
ed control conguration. This terminal is energized in the 
heating mode when the combustion air inducer is operat-
ing. Any humidier rated up to one amp can be connect-
ed to this terminal with the neutral leg of the circuit being 
connected  to  one  of  the  provided  neutral  terminals.  If  a 
humidier rated at greater than one amp is connected to 
this terminal, it is necessary to use an external relay relay. 
One 24V ”H” 1/4”  spade  terminal is provided on the fur-
nace integrated control. See gure 30 for integrated con-
trol conguration. The terminal is energized in the heating 
mode when the combustion air inducer  is  operating and 
the pressure switch is closed. Any humidier rated up to 
0.5 amp can be connected to this terminal with the ground 
leg of the circuit connected to ground or the ”C” terminal. 
Generator Use - Voltage Requirements
The following requirements must be kept in mind when 
specifying a generator for use with this equipment:
•   The furnace requires 120 volts + 10% (Range: 108 volts 
to 132 volts).
•   The furnace operates at 60 Hz + 5% (Range: 57 Hz to 
63 Hz).
•   The furnace integrated control requires both polarity 
and proper ground. Both polarity and proper grounding 
should be checked before attempting to operate the fur-
nace on either permanent or temporary power.
•   Generator should have a wave form distortion of less 
than 5% total harmonic distortion.